32
¦Partialis. 1 (ES) ¦ compressor has been selected and the Energy Saving
¦Position : 000 U% ¦ option has been adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
PARZ1ED_2 (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦- Partialisations AL¦ the first compressor partialisation if two
¦Partialis. 1 (DE) ¦ compressors have been selected and the Energy
¦Position : 000 U% ¦ Saving option has not been adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
PARZ2ED_2 (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦- Partialisations AL¦ the second compressor partialisation if only one
¦Partialis. 2 (DE) ¦ compressor has been selected and the Energy Saving
¦Position : 000 U% ¦ option has not been adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
PARZ1ES_2 (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦- Partialisations AL¦ the first compressor partialisation if two
¦Partialis. 1 (ES) ¦ compressors have been selected and the Energy
¦Position : 000 U% ¦ Saving option has been adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
PARZ2ES_2 (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦- Partialisations AL¦ the second compressor partialisation if two
¦Partialis. 2 (ES) ¦ compressors have been selected and the Energy
¦Position : 000 U% ¦ Saving option has been adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
RIT_COMP1 (USER BRANCH)
+--------------------+ Setting of the minimum time lapse between the
¦-- Compressors AL¦ deactivation and the activation of the same
¦Minimum Run-Time ¦ compressor.
¦Before Comp. Stop : ¦
¦ 0000 seconds ¦
+--------------------+
RIT_COMP2 (USER BRANCH)
+--------------------+ Setting of the minimum working time of the single
¦-- Compressors AL¦ compressor .
¦Compressor Working ¦
¦Minimum Time: ¦
¦ 0000 seconds ¦
+--------------------+
RIT_COMP3BIS (USER BRANCH)
+--------------------+ Setting of the minimum time lapse between a start
¦-- Compressors AL¦ and the following one of the same compressor.
¦Time Between Starts ¦
¦of Same Compressor: ¦
¦ 0000 seconds ¦
+--------------------+
RIT_COMP3 (USER BRANCH)
+--------------------+ Setting of the necessary time to detect the low
¦-- Compressors AL¦ pressure alarm.
¦Low Pressure Alarm ¦
¦Delayed for: ¦
¦ 0000 seconds ¦
+--------------------+
RIT_COMP4 (USER BRANCH)
+--------------------+ Setting of the minimum time lapse between the start
¦-- Compressors AL¦ of one compressor and the start of the following
¦Time Between Starts ¦ one if two compressors have been selected.
¦of 2 Different Comp.¦
¦ 0000 seconds ¦
+--------------------+
COMPROT (USER BRANCH)
+--------------------+ Setting of compressors rotation.
¦-- Compressors AL¦
¦Automatic Rotation ¦

Other manuals for Carel pCO