31
¦- 3-Point Valves AL¦ cooling 3-point valve, if it has been selected.
¦Cooling 3-P Valve ¦
¦Start : 000 U%¦
¦End : 000 U%¦
+--------------------+
RAMPE43 (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦- 3-Point Valves AL¦ heating 3-point valve, if it has been selected.
¦Heating 3-P Valve ¦
¦Start : 000 U%¦
¦End : 000 U%¦
+--------------------+
RAMPE53 (USER BRANCH)
+--------------------+ Setting of Running time or opening time of 3-point
¦- 3-Point Valves AL¦ valves.
¦Running Time of ¦
¦3-Point Valve : ¦
¦ 000 seconds ¦
+--------------------+
COMP1ED (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦-- Compressors AL¦ the first compressor if only one compressor has
¦Compressor 1 (DE) ¦ been selected and the Energy Saving option has not
¦Position : 000 U% ¦ been adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
COMP1ES (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦-- Compressors AL¦ the first compressor if only one compressor has
¦Compressor 1 (ES) ¦ been selected and the Energy Saving option has not
¦Position : 000 U% ¦ been adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
COMP1ED_2 (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦-- Compressors AL¦ the first compressor if two compressors have been
¦Compressor 1 (DE) ¦ selected and the Energy Saving option has not been
¦Position : 000 U% ¦ adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
COMP2ED_2 (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦-- Compressors AL¦
¦Compressor 2 (DE) ¦ litati due compressors e Energy Saving non
¦Position : 000 U% ¦ abilitato.
¦Hysteresis : 000 U% ¦
+--------------------+
COMP1ES_2 (USER BRANCH)
+--------------------+ Setting dei valori di accensione e di
¦-- Compressors AL¦ spegnimento del primo compressor se abili-
¦Compressor 1 (ES) ¦ tati due compressors e Energy Saving abili-
¦Position : 000 U% ¦ tato.
¦Hysteresis : 000 U% ¦
+--------------------+
COMP2ES_2 (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦-- Compressors AL¦ the second compressor if two compressors have been
¦Compressor 2 (ES) ¦ selected and the Energy Saving option has been
¦Position : 000 U% ¦ adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
PARZ1ED (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦- Partialisations AL¦ the first compressor partialisation if only one
¦Partialis. 1 (DE) ¦ compressor has been selected and the Energy Saving
¦Position : 000 U% ¦ option has not been adopted.
¦Hysteresis : 000 U% ¦
+--------------------+
PARZ1ES (USER BRANCH)
+--------------------+ Setting of the values of activation/deactivation of
¦- Partialisations AL¦ the first compressor partialisation if only one