71
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index Display description Description Default UOM Values
……
Egbb01
Device present ChillBooster function enable (line 2) NO --- NO / YES
Deactivation when fan-
spower falls under
Fans capacity under which ChillBooster is deactivated (line 2) 95 % 0…100
……
Mask index Display description Description Default UOM Values
F.settings
Faaa01
Summer/Winter Enable Summer/Winter period management (line 1) NO --- NO / YES
Special days Enable special days management (line 1) NO --- NO / YES
Holiday periods Enable holiday period management (line 1) NO --- NO / YES
Faaa02
Begin Summer period beginning date (line 1) --- --- 01/Gen…31/Dic
End Summer period end date (line 1) --- --- 01/Gen…31/Dic
Faaa03 Day 01 Special day 1 date (line 1) --- --- 01/Gen…31/Dic
……
Faaa04 Day 10 Special day 10 date (line 1) --- --- 01/Gen…31/Dic
Faaa05
P1 Holiday period P1 beginning date (line 1) --- --- 01/Gen…31/Dic
--- Holiday period P1 end date (line 1) --- --- 01/Gen…31/Dic
……
P5 Holiday period P5 beginning date (line 1) --- --- 01/Gen…31/Dic
--- Holiday period P5 end date (line 1) --- --- 01/Gen…31/Dic
Faab01
Date format Date format DD/MM/YY --- ----
DD/MM/YY
MM/DD/YY
YY/MM/DD
Faab02/Faab03/
Faab04
Hour Hour and minute
Date Date … …
Day (display only) Day of the week calculated from current date Monday… Sunday
Faab05
Daily saving time Enable daylight saving time DISABLE --- DISABLE / ENABLE
Transition time O set time 60 --- 0 to 240
Start, ... Starting week, day and month and hour for daylight saving time
End, ... End week, day and month and hour for daylight saving time
Fb01 Language Current language ENGLISH ---
Fb02
Disable language mask at
start-up
Disable the change language screen at start-up YES --- NO / YES
Countdown Starting value for countdown, time change language screen active. 60 s 0…60
Fb03
Main mask selection Main screen selection LINE 1 --- LINE 1 / LINE 2
DOUBLE SUCTION
DOUBLE CONDENSER
Fca01
Address Address of the controller in a supervisory system network (line 1) 196 --- 0 to 207
Protocol Supervisor communication protocol (line 1) pRACK
MANAGER
--- --
CAREL SLAVE LOCAL
CAREL SLAVE REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
Baudrate Supervisor communication baud rate (line 1) 19200 --- 1200 to 19200
Fca02
Address Address of the controller in a supervisory system network (line 1) 1 --- 0…207
Protocol Supervisor communication protocol (line 1)
CAREL ---
---
CAREL SLAVE LOCAL
MODBUS SLAVE
pRACK MANAGER
Baudrate Supervisor communication baud rate (line 1) 19200 --- 1200…19200
Fd01
Insert password Password 0000 --- 0…9999
Logged as (display only) Current password level --- --- User, Service, Manufacturer
Fd02 Logout Logout NO --- NO / YES
Fd03
User User password 0000 --- 0…9999
Service Service password 1234 --- 0…9999
Manufacturer Manufacturer password 1234 --- 0…9999
The following parameters refer to line 2, for details see the corresponding parameters for line 1 above
Fcb01
Address Enable summer/winter period management (line 2) 196 --- 0 to 207
Protocol Enable special days management (line 2) pRACK
MANAGER
--- --
CAREL SLAVE LOCAL
CAREL SLAVE REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
Baudrate Enable holiday period management (line 2) 19200 --- 1200 to 19200
Fcb01
Address Enable summer/winter period management (line 2)
1 --- 0…207
Protocol Enable special days management (line 2)
MODBUS
SLAVE
---
---
CAREL SLAVE LOCAL
MODBUS SLAVE
pRACK MANAGER
Baudrate Enable holiday period management (line 2)
19200 --- 1200…19200
Mask index Display description Description Default UOM Values
G.Safety
Gba01 Prevent enable Enable condensing pressure prevent (line 1) NO --- NO / YES
Gba02
Setpoint Condensing pressure prevent threshold (line 1) 0.0 barg … (**)
Diff erential Condensing pressure prevent diff erential (line 1) 0.0 barg 0.0 to 99.9
Decrease compressor
power time
Decreasing capacity time (line 1) 0 s 0…999
Gba03
Enable Heat Reclaim as
rst prevent step
Enabling heat recovery as fi rst stage for condensing HP prevent
(line 1)
NO --- NO / YES
Off set HeatR. Off set between heat recovery and prevent setpoint (line 1) 0.0 barg 0.0 to 99.9

Table of Contents