71
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index Display description Description Default UOM Values
…… … ………
Egbb01
Device present ChillBooster function enable (line 2) NO --- NO / YES
Deactivation when fan-
spower falls under
Fans capacity under which ChillBooster is deactivated (line 2) 95 % 0…100
…… … ………
Mask index Display description Description Default UOM Values
F.settings
Faaa01
Summer/Winter Enable Summer/Winter period management (line 1) NO --- NO / YES
Special days Enable special days management (line 1) NO --- NO / YES
Holiday periods Enable holiday period management (line 1) NO --- NO / YES
Faaa02
Begin Summer period beginning date (line 1) --- --- 01/Gen…31/Dic
End Summer period end date (line 1) --- --- 01/Gen…31/Dic
Faaa03 Day 01 Special day 1 date (line 1) --- --- 01/Gen…31/Dic
…… … ………
Faaa04 Day 10 Special day 10 date (line 1) --- --- 01/Gen…31/Dic
Faaa05
P1 Holiday period P1 beginning date (line 1) --- --- 01/Gen…31/Dic
--- Holiday period P1 end date (line 1) --- --- 01/Gen…31/Dic
…… ………
P5 Holiday period P5 beginning date (line 1) --- --- 01/Gen…31/Dic
--- Holiday period P5 end date (line 1) --- --- 01/Gen…31/Dic
Faab01
Date format Date format DD/MM/YY --- ----
DD/MM/YY
MM/DD/YY
YY/MM/DD
Faab02/Faab03/
Faab04
Hour Hour and minute … … …
Date Date … … …
Day (display only) Day of the week calculated from current date … … Monday… Sunday
Faab05
Daily saving time Enable daylight saving time DISABLE --- DISABLE / ENABLE
Transition time Off set time 60 --- 0 to 240
Start, ... Starting week, day and month and hour for daylight saving time … … …
End, ... End week, day and month and hour for daylight saving time … … …
Fb01 Language Current language ENGLISH --- …
Fb02
Disable language mask at
start-up
Disable the change language screen at start-up YES --- NO / YES
Countdown Starting value for countdown, time change language screen active. 60 s 0…60
Fb03
Main mask selection Main screen selection LINE 1 --- LINE 1 / LINE 2
DOUBLE SUCTION
DOUBLE CONDENSER
Fca01
Address Address of the controller in a supervisory system network (line 1) 196 --- 0 to 207
Protocol Supervisor communication protocol (line 1) pRACK
MANAGER
--- --
CAREL SLAVE LOCAL
CAREL SLAVE REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
Baudrate Supervisor communication baud rate (line 1) 19200 --- 1200 to 19200
Fca02
Address Address of the controller in a supervisory system network (line 1) 1 --- 0…207
Protocol Supervisor communication protocol (line 1)
CAREL ---
---
CAREL SLAVE LOCAL
MODBUS SLAVE
pRACK MANAGER
Baudrate Supervisor communication baud rate (line 1) 19200 --- 1200…19200
Fd01
Insert password Password 0000 --- 0…9999
Logged as (display only) Current password level --- --- User, Service, Manufacturer
Fd02 Logout Logout NO --- NO / YES
Fd03
User User password 0000 --- 0…9999
Service Service password 1234 --- 0…9999
Manufacturer Manufacturer password 1234 --- 0…9999
The following parameters refer to line 2, for details see the corresponding parameters for line 1 above
Fcb01
Address Enable summer/winter period management (line 2) 196 --- 0 to 207
Protocol Enable special days management (line 2) pRACK
MANAGER
--- --
CAREL SLAVE LOCAL
CAREL SLAVE REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
Baudrate Enable holiday period management (line 2) 19200 --- 1200 to 19200
Fcb01
Address Enable summer/winter period management (line 2)
1 --- 0…207
Protocol Enable special days management (line 2)
MODBUS
SLAVE
---
---
CAREL SLAVE LOCAL
MODBUS SLAVE
pRACK MANAGER
Baudrate Enable holiday period management (line 2)
19200 --- 1200…19200
Mask index Display description Description Default UOM Values
G.Safety
Gba01 Prevent enable Enable condensing pressure prevent (line 1) NO --- NO / YES
Gba02
Setpoint Condensing pressure prevent threshold (line 1) 0.0 barg … … (**)
Diff erential Condensing pressure prevent diff erential (line 1) 0.0 barg … 0.0 to 99.9
Decrease compressor
power time
Decreasing capacity time (line 1) 0 s 0…999
Gba03
Enable Heat Reclaim as
fi rst prevent step
Enabling heat recovery as fi rst stage for condensing HP prevent
(line 1)
NO --- NO / YES
Off set HeatR. Off set between heat recovery and prevent setpoint (line 1) 0.0 barg … 0.0 to 99.9