Table 1 — 19XL Compressor/Motor Weights
MOTOR
SIZE
ENGLISH SI
Compressor
Weight (lb)
Stator Weight (lb) Rotor Weight (lb)
End Bell
Cover (lb)
Compressor
Weight (kg)
Stator Weight (kg) Rotor Weight (kg)
End Bell
Cover (kg)
60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz
CB 2660 1135 1147 171 233 250 1208 515 520 78 106 114
CC 2660 1143 1150 197 239 250 1208 518 522 90 109 114
CD 2660 1153 1213 234 252 250 1208 523 551 106 114 114
CE 2660 1162 1227 237 255 250 1208 528 557 108 116 114
CL 2660 1202 1283 246 270 250 1208 546 582 112 123 114
CM 2660 1225 1308 254 275 250 1208 556 594 115 125 114
CN 2660 1276 1341 263 279 250 1208 579 609 119 127 114
CP 2660 1289 1356 266 284 250 1208 585 616 121 129 114
CQ 2660 1306 1363 273 287 250 1208 593 619 124 130 114
CR 2660 1335 1384 282 294 250 1208 606 628 128 133 114
NOTE: For medium voltage motors add 85 lbs (39 kg) to above for 60-Hz motors and 145 lbs (66 kg) for 50-Hz motors.
Total compressor/motor weight is the sum of the compressor, stator, rotor, and end bell cover weight. Compressor
weight includes suction and discharge elbow weights.
Table 2 — 19XL Component Weights
COMPONENT lb kg
Suction Elbow* 54 25
Discharge Elbow* 46 21
Control Cabinet† 30 14
Optional Mounted Starter** 500 227
*Included in total compressor weight.
†Included in total cooler weight.
**Weight of optional factory-mounted starter is not included and must be
added to heat exchanger weights.
Table 3 — 19XL Heat Exchanger Weights*
CODE
ENGLISH SI
Rigging Wt (lb)† Chiller Charge Rigging Wt (kg)† Chiller Charge
Cooler
Only
Condenser
Only
Refrigerant (lb) Water (gal.)
Cooler
Only
Condenser
Only
Refrigerant (kg) Water (L)
Cooler
Condenser** Cooler Condenser
Cooler
Condenser** Cooler Condenser
R-22 R-134A R-22 R-134A
40 5340 4855 750 550 350 53 56 2422 2202 341 250 159 201 212
41 5485 5010 800 600 350 58 62 2488 2272 363 272 159 220 235
42 5655 5180 900 650 350 64 68 2565 2350 408 295 159 242 257
43 5845 5370 1000 700 350 71 75 2651 2436 454 318 159 269 284
50 7020 6750 1150 750 350 79 84 3184 3062 522 341 159 299 318
51 7255 6960 1250 850 350 87 92 3291 3157 568 386 159 329 348
52 7510 7200 1400 950 350 96 101 3406 3266 636 431 159 363 382
53 7770 7475 1500 1000 350 104 110 3524 3391 681 454 159 394 416
55 8510 8345 1410 1060 490 104 112 3860 3785 640 481 222 395 423
56 8845 8635 1710 1160 490 115 123 4012 3917 776 527 222 438 466
57 9205 8980 2010 1260 490 128 135 4175 4073 913 572 222 486 513
58 9575 9370 2210 1410 490 140 149 4343 4250 1003 640 222 531 565
*This data is based on the standard waterbox weight at 150 psi (1034 kPa) pressure.
†Rigging weights are for standard tubes of standard wall thickness. For special tubes, refer to the 19XL Computer Selection Program.
**Refrigerant charge listed is the same for both HCFC-22 and HFC-134a.
Table 4 — Additional Heat Exchanger Weight for Marine Waterboxes*
HEAT EXCHANGER
FRAME, PASS
ENGLISH SI
Rigging Wt (lb) Water Volume (gal.) Rigging Wt (kg) Water Volume (L)
Cooler Condenser Cooler Condenser Cooler Condenser Cooler Condenser
FRAME 4, 2 PASS 1115 660 69 51 506 300 261 193
FRAME 4,1&3PASS 2030 1160 138 101 922 527 524 384
FRAME 5, 2 PASS 1220 935 88 64 554 424 331 243
FRAME 5,1&3PASS 2240 1705 175 128 1017 774 663 486
*Add to heat exchanger weights for total weight.