10
Fig. 7 — 19XR Pumpout System Wiring Schematic
a19-2447
LOW PRESSURE CONTROL
NC OPEN < 7 psia (-15.7 in. HG)
CLOSE > 9 psia (-11.6 in. HG)
HIGH PRESSURE
SAFETY
NC OPEN > 185psig
CONTROL POWER
TRANSFORMER
XFMR-1
69 VA
PUMP OUT
COMPRESSOR
CRANKCASE HEATER
240-600v
27-40 WATT
COPELAND PN 081-0031-03
WHT
RED
ORN
HIGH LEVEL
GAGE ALARM
(NC-OPEN AT
90% STORAGE
TANK LEVEL)
WHT
X2
C
5
4
X2
X2
1
X1
FU3
0.5A
H1
H4
FU1
FU2
0.25A
0.25A
GND
2
2
3
SS-1
OFF
AUTO ON
2
L2
L1
8
7
HTR-1
MTR-1
2 OL
2 OL
2 OL
C
C
C
LEVEL GAGE
ALARM SWITCH
NO
NC
LEGEND
C—Contactor
FU Fuse
GND Ground
HTR Heater
MTR Motor
NC Normally Closed
OL Overload
SS Selector Switch
Fig. 8 — Pumpout Unit Wiring Schematic
a19-2448
LOW PRESSURE CONTROL
NC OPEN < 7 psia {-15.7 in. HG}
CLOSE > 9 psia {-11.6 in. HG}
HIGH PRESSURE
SAFETY
NC OPEN > 185psig
CONTROL POWER
TRANSFORMER
XFMR-1
69 VA
PUMP OUT
COMPRESSOR
CRANKCASE HEATER
240-600v
27-40 WATT
X2
C
5
4
X2
X2
1
X1
FU3
0.5A
H1
H4
FU1
FU2
0.25A
0.25A
GND
2
2
3
SS-1
OFF
AUTO ON
2
L2
L1
8
7
HTR-1
MTR-1
2 OL
2 OL
2 OL
C
C
C
LEGEND
C—Contactor
FU Fuse
GND Ground
HTR Heater
MTR Motor
NC Normally Closed
OL Overload
SS Selector Switch

Related product manuals