EasyManua.ls Logo

Carrier 23XL - Page 100

Carrier 23XL
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
100
AUX Auxiliary
BR Bridge Rectifier
CB Circuit Breaker
COMM Communication
COND Condenser
CPU Central Processing Unit
CVC Chiller Visual Controller
CT Current Transformer
EVAP Evaporator
FU Fuse
G—Ground
L—Main Supply Power
LL Control Power Supply
M—Contactor
O/L Overload Reset
S—Contactor
SCR Silicone Controller Rectifier
ST Shunt Trip
TB Ter minal B lock
Wire Node Symbol may
have terminal block
Benshaw supplied terminal
block
Terminal Strip
Power Connection
PC Board Terminals
Twisted Pair
Twisted Shielded Pair
Shield Wire
Field Wiring
NOTES:
LED status with power applied and prior to run command. “ON
“OFF”
Transformer T1 primary fuses FU1/FU2 value dependent on system voltage and
model, per Chart 1. Transformer connections per transformer nameplate connec-
tion diagram.
MOVs are used on power stack assemblies for system voltages of 200 through
460 vac (as shown). Resistor/capacitor networks (DVDTs) are used on power
stack assemblies in place of MOVs for a system voltage of 575 vac (not shown).
K3 relay shown in deenergized state. K3 contact will close when power is applied.
K3 contact will open on stop command or system faul
1
2
3
4
LEGEND
Fig. 49 Benshaw, Inc. Solid-State Unit Mounted Starter Wiring Schematic (Low Voltage) (cont)