EasyManua.ls Logo

Carrier Ecologic 30HXC076-271 User Manual

Carrier Ecologic 30HXC076-271
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Controls, Start-Up, Operation,
Service, and Troubleshooting
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical compo-
nents, and equipment location (roof, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment, and any other safety precautions that apply. Fol-
low all safety codes. Wear safety glasses and work gloves.
Use care in handling, rigging, and setting this equipment,
and in handling all electrical components.
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation
and service. There may be more than one disconnect
switch. Tag all disconnect locations to alert others not
to restore power until work is completed.
This unit uses a microprocessor-based electronic con-
trol system. Do not use jumpers or other tools to short
out components, or to bypass or otherwise depart from
recommended procedures. Any short-to-ground of the
control board or accompanying wiring may destroy the
electronic modules or electrical components.
To prevent potential damage to heat exchanger tubes al-
ways run fluid through heat exchangers when adding or
removing refrigerant charge.
DO NOT VENT refrigerant relief valves within a build-
ing. Outlet from relief valves must be vented outdoors
in accordance with the latest edition of ANSI/ASHRAE
(American National Standards Institute/American Soci-
ety of Heating, Refrigeration and Air Conditioning En-
gineers) 15 (Safety Code for Mechanical Refrigeration).
The accumulation of refrigerant in an enclosed space
can displace oxygen and cause asphyxiation. Provide ad-
equate ventilation in enclosed or low overhead areas.
Inhalation of high concentrations of vapor is harmful
and may cause heart irregularities, unconsciousness or
death. Misuse can be fatal. Vapor is heavier than air and
reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition
products are hazardous.
DO NOT attempt to unbraze factory joints when ser-
vicing this equipment. Compressor oil is flammable and
there is no way to detect how much oil may be in any
of the refrigerant lines. Cut lines with a tubing cutter as
required when performing service. Use a pan to catch
any oil that may come out of the lines and as a gage for
how much oil to add to system. DO NOT re-use com-
pressor oil.
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
GENERAL ...................................2
MAJOR SYSTEM COMPONENTS ..............3
Processor Module (PSIO-1) ...................3
DSIO-HV Relay Module .......................3
Electronic Expansion Device Module .........3
Compressor Protection Module (CPM) .........3
PSIO-2 (8052) Module ........................3
Keypad and Display Module
(Also Called HSIO-II) .......................3
Control (LOR) Switch .........................3
OPERATION DATA ..........................3-42
Electronic Expansion Device (EXD) ...........3
EXV OPERATION
ECONOMIZER OPERATION
Oil Pumps ...................................4
Motor Cooling ...............................4
Back Pressure Valve (30GX and 30HXA only) ..4
Sensors .....................................4
Compressor Protection Module (CPM) .........4
OUTPUTS
INPUTS
Wye-Delta vs Across-the-Line (XL)
Starting Option ............................5
Capacity Control .............................6
MINUTES LEFT FOR START
MINUTES OFF TIME
LOADING SEQUENCE
CLOSE CONTROL
LEAD/LAG DETERMINATION
CAPACITY SEQUENCE DETERMINATION
MINIMUM LOAD VALVE
CAPACITY CONTROL OVERRIDES
Head Pressure Control .......................8
GENERAL
AIR COOLED UNITS (30GX)
WATER COOLED UNITS (30HX)
ADJUSTING PID ROUTINES
Cooler and Condenser (30HXC)
Pump Control .............................10
30GX080-265
30HXA,HXC076-271
ECOLOGIC™ Air-Cooled and Fluid Cooled Chillers
50/60Hz
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5c
PC 903 Catalog No. 533-062 Printed in U.S.A. Form 30G,H-3T Pg 1 1-98 Replaces: 30G,H-2T
Series 0,1,2

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Carrier Ecologic 30HXC076-271 and is the answer not in the manual?

Carrier Ecologic 30HXC076-271 Specifications

General IconGeneral
BrandCarrier
ModelEcologic 30HXC076-271
CategoryChiller
LanguageEnglish

Summary

SAFETY CONSIDERATIONS

General Safety Precautions

Covers hazards during installation, servicing, and general safety practices like wearing PPE.

Electrical Hazard Warnings

Multiple warnings regarding electrical shock, control system bypass, and wiring.

Refrigerant and Oil Handling Warnings

Warnings about venting refrigerant, flammable oil, and handling refrigerant lines.

MAJOR SYSTEM COMPONENTS

Processor Module (PSIO-1)

Core module controlling operation, receiving input/output from other modules.

DSIO-HV Relay Module

Controls oil heater, outdoor fan, and minimum load on 30GX units.

Electronic Expansion Device Module

Operates electronic expansion devices and reports status.

Compressor Protection Module (CPM)

Monitors compressor safeties and controls outputs for each compressor.

PSIO-2 (8052) Module

Used as an input/output module without operating software.

Keypad and Display Module (HSIO-II)

Interface for operator communication and control.

Control (LOR) Switch

Selects unit operating mode (Local, Off, Remote).

OPERATION DATA

Electronic Expansion Device (EXD)

Controls refrigerant flow via stepper motor for precise level maintenance.

Oil Pumps

Prelubricates compressors before start-up to ensure sufficient oil pressure.

Motor Cooling

Uses flash gas or solenoid valve to cool compressor motor windings.

Back Pressure Valve (30GX and 30HXA only)

Ensures sufficient system pressure for oil return to the compressor.

Sensors

Gathers data for chiller operation control, monitoring pressure, temperature, and liquid level.

Wye-Delta vs Across-the-line (XL) Starting Option

Wye-Delta Starting

Uses a factory-installed starter assembly with 3 contactors for reduced starting current.

Across-the-Line (XL) Starting

Simplest starting method using a single contactor for motors designed for continuous operation.

Capacity Control

MINUTES LEFT FOR START

Displays time remaining before unit start, influenced by various conditions.

MINUTES OFF TIME

User-configurable delay for unit operation after power restoration or compressor restart.

LOADING SEQUENCE

Describes the sequence for starting compressors and loaders for optimal chiller efficiency.

CLOSE CONTROL

LEAD/LAG DETERMINATION

Configurable choice for determining which circuit leads or lags based on starts and operating hours.

CAPACITY SEQUENCE DETERMINATION

Configurable as equal or staged circuit loading for capacity step changes.

MINIMUM LOAD VALVE

Initiates first stage of capacity and is used for the last stage before circuit shutdown.

CAPACITY CONTROL OVERRIDES

Overrides that modify the normal operation of the capacity control routine.

Slow Change Override

Ramp Loading

Limits the rate of change of leaving fluid temperature to prevent compressor overloading.

Low Entering Fluid Temperature Unloading

Reduces unit capacity when entering fluid temperature is below the control point.

Low Discharge Superheat

Adjusts EXV opening or unloads circuit based on discharge superheat levels.

Low Saturated Suction Temperature

Prevents unit capacity increase or shuts down circuit to avoid cooler freezing.

High Condensing Temperature Unloading

Cycles loaders or shuts down compressor to control condensing temperature.

MOP (Maximum Operating Pressure) Override

Reduces capacity stages or lowers EXV position as system pressures approach set parameters.

Head Pressure Control

GENERAL

Controls condenser fans or water valves to maintain saturated condensing temperature.

AIR COOLED UNITS (30GX)

Details fan staging for air-cooled units, referencing Fig. 5.

No Motormaster® Control

Fan Staging Control

Controls condenser fans based on Saturated Condensing Temperature and Head Pressure Set Point.

Motormaster® Control

Optional controller for low-ambient operation, managing head pressure via PID loop.

WATER-COOLED UNITS (30HX)

Direct or Reverse-Acting Water Valves

Controls water valves using 4-20 mA or 2-10 VDC signals based on condensing temperature.

Cooler and Condenser (30HXC) Pump Control

Cooler Pump Control

Controls cooler pump based on occupied mode or freeze protection.

Condenser Pump Control

Two Control Methods

Describes two methods for condenser pump control: occupied mode or compressor start/stop.

Cooler Heater Control

Cooler Heater Operation

Activates cooler heaters only when the chiller is in a saturated suction temperature freeze condition.

ACCESSING FUNCTIONS AND SUBFUNCTIONS

Keypad Button Descriptions

Brief description of the function and operative keys on the keypad.

Subfunction Access Example

Provides an example of how to navigate and access subfunctions.

Automatic Default Display

Describes the rotating display that appears after 10 minutes of inactivity.

Functions and Subfunctions Directory

Status Function (STAT)

Displays diagnostic codes and current operating information about the machine.

Test Function (TEST)

Used for testing operating analog and discrete outputs.

Schedule Function (SCHD)

Used for entering occupied/unoccupied schedules for unit operation.

Service Function (SRVC)

Used for entering configuration information and enabling manual control.

History Function (HIST)

Used for displaying run time, cycles, and previous alarms.

Set Point Function (SET)

Used for entering operating set points and day/time information.

STATUS FUNCTION

Alarms/Alerts

Messages indicating faults that cause unit shutdown, termination, or default value usage.

General Parameters

Displays control mode, run status, CCN status, and current alarms.

Circuit A Analog Values

Displays current system operating conditions such as pressures and temperatures for Circuit A.

Circuit A Discrete Inputs and Outputs

Shows On/Off status of compressor(s), loaders, solenoids, and pumps for Circuit A.

Unit Analog Parameters and Temperature Reset

Miscellaneous Inputs and Outputs

Shows status of condenser fans, demand limit settings, and pump status.

Modes

Indicates the unit's operating status, such as Local On/Off or CCN On.

Capacity Control

Displays load/unload factor, control point, and leaving water temperature.

Dual Chiller

Displays dual chiller control status, including Master/Slave configuration and lead/lag information.

Status Function and Subfunction Directory

1 Alarms

Displays current alarms and allows resetting them.

2 General Parameters

Displays control mode, run status, CCN status, and current alarms.

3 Circuit A Analog Values

Displays total capacity, discharge pressure, suction pressure, and oil pressure for Circuit A.

Status Function and Subfunction Directory (cont)

3 Circuit A Analog Valves (cont)

Displays SAT condensing temp, saturated suction temp, EXV percent open, and water valve position for Circuit A.

4 Circuit A Discrete Inputs/Outputs

Shows compressor, loader, oil heater, and motor cooling solenoid status for Circuit A.

5 Circuit B Analog Values

Displays total capacity, discharge pressure, suction pressure, and oil pressure for Circuit B.

Status Function and Subfunction Directory (cont)

5 Circuit B Analog Valves (cont)

Displays motor temperature, SAT condensing temp, EXV percent open, and cooler level indicator for Circuit B.

6 Circuit B Discrete Inputs/Outputs

Shows compressor, loader, oil heater, and motor cooling solenoid status for Circuit B.

7 Unit Analog Parameters

Displays entering and leaving fluid temperatures for the cooler and condenser.

Status Function and Subfunction Directory (cont)

7 Unit Analog Parameters (cont)

Displays temperature reset, demand limit signals, and outdoor air temperature.

8 Misc. Inputs/Outputs

Shows status of condenser fans, demand limit switches, pump relays, and miscellaneous inputs.

9 Operating Modes

Indicates the unit's operating status, such as Local On/Off or CCN On.

Status Function and Subfunction Directory (cont)

9 Operating Modes (cont)

Lists various operating modes like Clock Off, Local On, CCN On, and Dual SP Active.

10 Capacity Control

Displays load/unload factor, control point, and leaving water temperature.

Status Function and Subfunction Directory (cont)

11 Dual Chiller

Displays dual chiller control status, including Master/Slave configuration and lead/lag information.

TEST FUNCTION

Discrete Output Testing

Tests operation of loaders, solenoids, oil pump, and fans.

EXV Valve Testing

Tests EXV motor operation and valve movement in 25% increments.

HISTORY FUNCTION

Displays machine operating hours, run time, and starts for the unit and compressors.

SET POINT FUNCTION

Allows entering and changing set points within fixed upper and lower limits.

Test Function and Subfunction Directory

1 Circuit A Discrete Output

Tests discrete outputs for Circuit A, including loaders and solenoids.

2 Circuit B Discrete Outputs

Tests discrete outputs for Circuit B, including loaders and solenoids.

3 Unit Discrete Output

Tests unit discrete outputs such as fans, cooler pump, condenser pump, and cooler heater.

Test Function and Subfunction Directory (cont)

3 Unit Discrete Output (cont)

Tests remote alarm outputs (currently not supported).

4 Valves and Motormaster

Tests EXV valve operation and fan speed for Motormaster controlled units.

History Function and Subfunction Directory

1 Operating Hours

Displays machine and compressor operating hours and starts.

2 Alarm History

Lists the 10 most recent alarms with descriptions, time, and date of occurrence.

Set Point Function and Subfunction Directory

1 Set Point Table

Allows setting of cooling, heating, head pressure, demand limit, and minutes off time.

2 Units

Selects imperial or metric units for temperature and pressure display.

3 Address

Displays target address and bus number for CCN configurations.

4 Time

Allows reading and changing the unit's date and time.

5 CCN Disable

Disables CCN control commands, allowing local mode operation.

Reading and Changing Chilled Fluid Set Point

SERVICE FUNCTION

Allows viewing and entering configuration data, including factory, field, and service configurations.

Password Protection of HSIO Configurable Service Points

Requires a password to modify configurations and use manual control subfunction.

Options Configuration Tables 1 and 2

Accesses configuration options for various chiller settings and features.

Temperature Reset, Demand Limit and Head Pressure PID Configurations

Allows configuration of temperature reset, demand limit, and head pressure PID settings.

Factory Configuration Codes

Allows entry into factory and service configuration codes for proper unit operation.

Transducer Calibration

Allows viewing transducer calibration information and performing calibration.

Manual Control Mode

Provides full control over compressors, loaders, and minimum load valve for manual operation.

Dual Chiller Configuration

Enables Master/Slave combination of chillers for coordinated operation.

Service Function and Subfunction Directory

1 Service Configuration

Configures chiller settings like unit type, compressor tonnage, and temperature setpoints.

2 Options Configuration 1

Configures cooler fluid select, minimum load valve select, and loading sequence.

3 Options Configuration 2

Configures cooling setpoint select, heating setpoint select, and ramp load select.

Service Function and Subfunction Directory (cont)

3 Options Configuration 2 (cont)

Configures clock control, OAT sensor select, and alarm reset select.

4 Reset Configuration Table

Configures cooling and heating reset types, demand limit, and deadband multiplier.

Service Function and Subfunction Directory (cont)

4 Reset Configuration Table (cont)

Configures loadshed group number, maximum loadshed time, and PID gains for water valve and motor master.

5 Factory Configuration Codes

Displays factory set configuration codes for unit setup.

7 Transducer Calibration

Allows calibration of pressure transducers for accurate readings.

Service Function and Subfunction Directory (cont)

8 Manual Control Table

Enables manual control of compressors, loaders, and minimum load valve.

9 Dual Chiller Configuration

Configures Master/Slave selection, slave address, and lead/lag balance for dual chiller systems.

Displaying Current Software Version

Software Version Display

Shows the Carrier Software Part Number and revision number.

Compressor Lead/Lag Configuration

Options Configuration 1

Configures cooler fluid select, minimum load valve select, and loading sequence.

Entering Configuration Codes

Factory Codes Entry

Provides keypad entry sequence for factory configuration codes.

Service Codes Entry

Provides keypad entry sequence for service configuration codes.

SCHEDULE FUNCTION

Occupied/Unoccupied Time Periods

Configures user-defined time periods for automatic switching between occupied and unoccupied modes.

Dual Set Point Control

Enables a second cooling set point for ice duty or unoccupied periods.

Schedule Function and Subfunction Directory

1 Ice Build Schedule

Configures schedules for ice build operations, including timed overrides.

2 Local Schedule

Configures local time schedules for occupied and unoccupied periods.

4 Holiday Configuration

Allows configuration of holiday start day and duration for schedule overrides.

5-33 Holiday Configuration

Allows configuration of 29 additional holiday periods.

Temperature Reset

Return Fluid Temperature Reset

Resets leaving fluid temperature based on return fluid temperature to optimize chiller efficiency.

External Temperature Reset

Resets leaving fluid temperature based on outdoor ambient temperature.

Externally Powered Reset (4 to 20 mA)

Resets leaving fluid temperature based on a 4 to 20 mA signal input.

Demand Limit

Demand Limit Types

Describes three types of demand limiting: switch, 4-20 mA signal, and CCN Loadshed.

Demand Limit (Switch Controlled, 30GX only)

Reduces maximum capacity based on the state of two switch inputs.

Setting External Temperature Reset

Cooling Reset Type Selection

Selects the type of reset (e.g., degrees reset, remote temp, CHW Delta T).

Select/Enable Reset Type

Enables or disables the selected reset type for cooling.

Setting Externally Powered Reset

Cooling Reset Type Selection

Configures cooling reset type for externally powered inputs.

Setting Return Fluid Temperature Reset

Cooling Reset Type Selection

Configures cooling reset type for return fluid inputs.

EXTERNALLY POWERED DEMAND LIMIT (4 to 20 mA Controlled)

Setting Demand Limit (4 to 20 mA Controlled)

Configures demand limit percentage and select 4-20 mA control.

Demand Limit (CCN Loadshed Controlled)

Configures loadshed group number, demand delta, and maximum loadshed time.

Setting Switch-Controlled Demand Limit

Demand Limit Select

Selects demand limit type (two-step switch, 4-20 mA, or CCN Loadshed).

TROUBLESHOOTING

Checking Display Codes

Checks diagnostic information in Status and Service functions for unit operation.

Unit Shutoff

Procedure to shut off the unit by moving the LOCAL/OFF/REMOTE switch.

Complete Unit Stoppage

Lists potential causes for complete unit stoppage, such as load satisfied or power failure.

Single Circuit Stoppage

Lists causes for single circuit stoppage, such as low oil pressure or thermistor failure.

Restart Procedure

Steps for restarting the unit after a stoppage, including manual reset requirements.

POWER FAILURE EXTERNAL TO THE UNIT

Unit restarts automatically when power is restored.

Alarms and Alerts

Warnings of abnormal conditions assigned code numbers, displayed on HSIO.

Compressor Alarm/Alert Circuit

Explains how CPM processor controls compressor start/stop based on high-pressure switch.

Alarm and Alert Codes

CPM SUBCODES (xx)

Lists CPM specific alarms like High Pressure Switch Trip, No Motor Current, and Current Imbalance.

ALARM/ALERT CODE

Details specific alarm codes, their causes, actions taken, and probable causes.

Alarm and Alert Codes (cont)

CPM SUBCODES (xx) (cont)

Lists CPM specific alarms like Motor Over Temperature and Open Thermistor.

ALARM/ALERT CODE

Details specific alarm codes, their causes, actions taken, and probable causes for thermistor and pressure transducer failures.

Alarm and Alert Codes (cont)

ALARM/ALERT CODE

Details specific alarm codes for oil pressure transducer failure, economizer transducer failure, and voltage issues.

Alarm and Alert Codes (cont)

ALARM/ALERT CODE

Details alarm codes for condenser freeze protection, loss of condenser flow, illegal configuration, and cooler pump interlock.

Alarm and Alert Codes (cont)

ALARM/ALERT CODE

Details alarm codes for high discharge pressure, low leaving chilled water temperature, and low oil level.

Hardware Point Communications Loss/Action Taken

CONTROL POINT NAME

Lists control points and the action taken when communication is lost.

Illegal Configurations Recognized by PSIO-1

CODE NUMBER

Lists illegal configuration codes and their descriptions.

EXD Troubleshooting Procedure

EXV Motor Operation Check

Checks EXV motor operation and lead screw movement for proper valve function.

EXV Output Signals Test

Checks EXV output signals at appropriate terminals on the EXV driver module.

INSPECTING/OPENING ELECTRONIC EXPANSION VALVES

Physical Operation Check

Steps to check the physical operation of an EXV, including motor and lead screw movement.

EXV Test Step Access

Accessing the appropriate EXV test step via the HSIO keypad.

Additional Items to Check

Checks float assembly, bubbler tube, and wiring for proper economizer function.

INSPECTING/OPENING ECONOMIZERS

Physical Operation Check

Steps to check the physical operation of an economizer.

EXV Test Step Access

Accessing the appropriate EXV test step via the HSIO keypad.

Additional Items to Check

Checks float assembly, bubbler tube, and wiring for proper economizer function.

Servicing Coolers and Condensers

TUBE PLUGGING

Procedure for plugging leaky tubes until cooler retubing is necessary.

RETUBING

Guidelines for retubing heat exchangers, including torque specifications.

TIGHTENING COOLER/CONDENSER HEAD BOLTS

Procedure for tightening cooler/condenser head bolts with O-ring preparation.

Inspecting/Cleaning Heat Exchangers

COOLERS

Inspecting and cleaning cooler tubes, checking thermistors for corrosion or scale.

CONDENSERS (30HX Only)

Inspecting and cleaning condenser tubes, checking thermistors for corrosion or scale.

Water Treatment

Importance of proper water treatment to prevent corrosion, scaling, and algae.

Condenser Coils (30GX Only)

COIL CLEANING

Methods for cleaning condenser coils using vacuum, water, or compressed air.

Refrigerant Charging/Adding Charge

Indication of low charge on a 30HXC system

Factors to consider when checking for low refrigerant charge, including sight glass and EXV percent open.

To add charge to the 30HXC systems

Procedure for adding liquid refrigerant charge to 30HXC systems.

Oil Charging/Low Oil Recharging

Addition of oil charge to 30HX,GX systems

Procedure for adding oil to the system if low oil level alarms persist.

Maximum Oil Charges

Table listing maximum oil charges for different unit sizes.

Oil Filter Maintenance

REPLACING THE EXTERNAL OIL FILTER

Step-by-step procedure for replacing the external oil filter.

REPLACING THE INTERNAL OIL FILTER

Procedure for replacing the internal oil filter.

Compressor Changeout Sequence

Compressor Changeout Procedure

Detailed steps for changing compressors, including electrical and mechanical procedures.

BURNOUT CLEANUP PROCEDURE

Cleanup Steps

Steps to perform after a compressor motor burnout, including oil removal and filter replacement.

Moisture-Liquid Indicator

Moisture Indication and Filter Drier Replacement

Explains how to interpret moisture indicators and when to replace the filter drier.

Liquid Line Service Valve

Liquid Line Service Valve Function

Describes the function of the liquid line service valve for field charging.

Thermistors

Thermistor Performance Verification

Aids in verifying thermistor performance by providing resistance values at various temperatures.

Thermistor Replacement

Provides instructions for replacing thermistors, including liquid level sensors.

Pressure Transducers

Pressure Transducer Calibration

Details the procedure for calibrating pressure transducers using system pressure or atmospheric pressure.

Troubleshooting Transducer Issues

Guides on checking supply voltage and comparing readings to a calibrated gauge.

Safety Devices

Compressor Protection

Covers motor overload protection and compressor protection module functions.

Oil Separator Heaters (30GX)

Explains how oil separator heaters operate based on discharge gas temperature.

Cooler Protection

Details low water temperature safety and freeze protection for the cooler.

Relief Devices

Describes the location and function of fusible plugs and pressure relief valves.

Control Modules

RED LED & GREEN LED Indicators

Explains the meaning of LED indicators on PSIO and DSIO modules for proper operation.

Carrier Comfort Network (CCN) Interface

Provides information on connecting the chiller units to the CCN for communication.

Compressor Control Troubleshooting

Compressor Does Not Run

Lists symptoms and causes for compressors not running, with remedies.

Compressor Cycles Off on Low Pressure

Lists causes and remedies for compressors cycling off due to low pressure.

Compressor Shuts Down on High Pressure Control

Lists causes and remedies for compressors shutting down due to high pressure.

Unit Operates Long or Continuously

Lists causes and remedies for units operating longer than expected.

System Noises

Lists common system noises and their probable causes.

Compressor Loses Oil

Lists causes and remedies for compressors losing oil.

Hot Liquid Line / Frosted Liquid Line

Addresses issues related to hot liquid lines and frosted liquid lines.

Compressor Loaders Not Working Properly

Lists causes and remedies for compressor loaders not functioning correctly.

Replacing Defective Processor Module

PSIO-1 Module Replacement

Procedure for replacing a defective PSIO-1 module, including software and configuration transfer.

Winter Shutdown Preparation

Steps to prepare the chiller for winter shutdown, including draining fluid and filling with antifreeze.

PRE-START-UP PROCEDURE

System Check

Checklist for verifying auxiliary components, electrical connections, and refrigerant valves.

Phase Check

Procedure to check incoming power phasing and correct if necessary.

START-UP AND OPERATION

Actual Start-Up

Steps for performing an actual start-up under supervision, including setting temperature and pump operation.

Operating Sequence

Describes the chiller's operational sequence from start-up to capacity staging.

FIELD WIRING

Power Supply Wiring

Diagram showing power supply connections for control circuits.

Remote Alarm Relay Accessory Wiring

Wiring diagrams for remote alarm relay accessories.

Chilled Water Pump Relay Wiring

30HXA,C Wiring

Wiring diagram for chilled water pump relay on 30HXA,C units.

30GX Wiring

Wiring diagram for chilled water pump relay on 30GX units.

Ground Fault Interrupter-Convenience Outlet Accessory Wiring

Accessory Wiring Diagram

Wiring diagram for the ground fault interrupter convenience outlet accessory.

Oil Pump Motor Junction Box Wiring

Control Circuit Wiring

Wiring diagrams for oil pump motor junction box control circuits.

Minimum Load Valve Accessory Wiring

Minimum Load Control Circuit Wiring

Wiring diagrams for minimum load valve accessory control circuits.

Condenser Pump Relay Wiring

30HXC and Remote Condenser Fan On/Off Wiring

Wiring diagrams for condenser pump relay and remote condenser fan control.

Chilled Water Interlock and Flow Switch Input Wiring

Flow Switch Input Wiring

Wiring diagram for chilled water interlock and flow switch input.

Remote On/Off Switch Input Wiring

Remote On/Off Input Wiring

Wiring diagram for remote on/off switch input.

PSIO-2 Wiring for Accessories and Field-Installed Options, 30HX Units

4-20 mA Signal Generator Wiring

Wiring for 4-20 mA signal generators for temperature reset and demand limit.

Condenser Flow Switch and Remote Dual Setpoint Wiring

Wiring for condenser flow switch and remote dual setpoint inputs.

Outdoor Air Thermistor Wiring

Wiring for outdoor air thermistor field supplied input.

PSIO-2 Wiring for Accessories and Field-Installed Options, 30GX Units

4-20 mA Signal Generator Wiring

Wiring for 4-20 mA signal generators for demand limit and temperature reset.

Space Temperature Sensor and Demand Limit Switch Wiring

Wiring for space temperature sensor and demand limit switch inputs.

Motormaster® Option Wiring

Wiring diagrams for Motormaster option on Circuits A and B.

Compressor Must Trip Amps (Determined by CPM Modules)

2-Compressor Units

Table listing required must trip amps for CPM modules on 2-compressor units.

Compressor Must Trip Amps (Determined by CPM Modules) (cont)

2-Compressor Units (cont)

Continues the table of required must trip amps for CPM modules on 2-compressor units.

Compressor Must Trip Amps (Determined by CPM Modules) (cont)

3-Compressor Units

Table listing required must trip amps for CPM modules on 3-compressor units.

Compressor Must Trip Amps (Determined by CPM Modules) (cont)

2-Compressor Units

Tables detailing punch-out configurations and overload settings for CPM modules on 2-compressor units.

Compressor Protection Module Configuration Header Punch-Outs and Overload Settings (cont)

2-Compressor Units (cont)

Continues tables for punch-out configurations and overload settings for 2-compressor units.

Compressor Protection Module Configuration Header Punch-Outs and Overload Settings (cont)

3-Compressor Units

Tables detailing punch-out configurations and overload settings for CPM modules on 3-compressor units.

Compressor Protection Module Configuration Header Punch-Outs and Overload Settings (cont)

3-Compressor Units (cont)

Continues tables for punch-out configurations and overload settings for 3-compressor units.

Compressor Protection Module Configuration Header Punch-Outs and Overload Settings (cont)

3-Compressor Units (cont)

Continues tables for punch-out configurations and overload settings for 3-compressor units.

30HX COOLER PRESSURE DROP — ENGLISH

Unit Size Range

Indicates the unit size ranges for cooler pressure drop charts.

30HX COOLER PRESSURE DROP — SI

Unit Size Range

Indicates the unit size ranges for cooler pressure drop charts in SI units.

30HX CONDENSER PRESSURE DROP — ENGLISH

Unit Size Range

Indicates the unit size ranges for condenser pressure drop charts.

30HX CONDENSER PRESSURE DROP — SI

Unit Size Range

Indicates the unit size ranges for condenser pressure drop charts in SI units.

30GX080-176 COOLER PRESSURE DROP — ENGLISH

Unit Size Range

Indicates the unit size ranges for cooler pressure drop charts.

30GX080-176 COOLER PRESSURE DROP — SI

Unit Size Range

Indicates the unit size ranges for cooler pressure drop charts in SI units.

30GX205-265 COOLER PRESSURE DROP — ENGLISH

Unit Size Range

Indicates the unit size ranges for cooler pressure drop charts.

30GX205-265 COOLER PRESSURE DROP — SI

Unit Size Range

Indicates the unit size ranges for cooler pressure drop charts in SI units.

Typical System Components, 30GX, With Economizer

LEGEND

Defines symbols used in the system component diagrams.

Typical System Components, 30HX, Without Economizer

LEGEND

Defines symbols used in the system component diagrams.

SERVICE TRAINING

Packaged Service Training

Programs for increasing knowledge of equipment through video and materials.

Classroom Service Training

Hands-on training in labs for troubleshooting and callbacks.

START-UP CHECKLIST FOR 30GX,HX LIQUID CHILLERS

A. Preliminary Information

Collects basic job information, installing contractor, and equipment model/serial numbers.

B. Preliminary Equipment Check

Checks for shipping damage, unit installation, electrical wiring, and component connections.

C. Unit Start-Up

Verifies CWP starter, valve status, leak checks, voltage imbalance, and compressor running current.

Related product manuals