CL-5
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
23XL PIC II ISM_CONF TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Starter Type
(0=Full, 1=Red, 2=SS/VFD)
0 to 2 1
Motor Rated Line Voltage
200 to 13200 VOLTS 460
Volt Transformer Ratio: 1
1 to 35 1
Overvoltage Threshold
105 to 115 % 115
Undervoltage Threshold
85 to 95 % 85
Over/Under Volt Time
1 to 10 SEC 5
Voltage % Imbalance
1 to 10 % 10
Voltage Imbalance Time
1 to 10 SEC 5
Motor Rated Load Amps
10 to 5000 AMPS 200
Motor Locked Rotor Trip
100 to 60000 AMPS 1000
Locked Rotor Start Delay
1 to 10 cycles 5
Starter LRA Rating
100 to 60000 AMPS 2000
Motor Current CT Ratio: 1
3 to 1000 100
Current % Imbalance
5 to 40 % 15
Current Imbalance Time
1 to 10 SEC 5
3 Grnd Fault CT’s? (1=No)
0/1 NO/YES YES
Ground Fault CT Ratio: 1
150 150
Ground Fault Current
1 to 25 AMPS 15
Ground Fault Start Delay
1 to 20 cycles 10
Ground Fault Persistence
1 to 10 cycles 5
Single Cycle Dropout
0/1 DSABLE/ENABLE DSABLE
Frequency-60 Hz? (No=50)
0/1 NO/YES YES
Line Frequency Faulting
0/1 DSABLE/ENABLE DSABLE