STEP 6. Make Piping Connections
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal to avoid personal
injury or death. Use all service ports and open all
flow-- control devices, including solenoid valves.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
To prevent improper performance and/or unit component
failures, do not leave system open to atmosphere any longer
than minimum required for installation. POE oil in
compressor is extremely susceptible to moisture absorption.
Always keep ends of tubing sealed during installation.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. vertical
rise at service valve. Refrigerant tubing lengths up to 36 in.
may be buried without further special consideration. Do
not bury lines longer than 36 in.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
To prevent damage to unit or service valves observe the
following:
S Use a brazing shield.
S Wrap service valves with wet cloth or use a heat sink
material.
Outdoor units may be connected to indoor section using
accessory tubin g pack age o r field--supplied refrigerant grade
tubing of correct size and condition. Rated tubing diameters
shown in Table 1 recommended up to 80 ft. See Product Data
for acceptable alternates vapor diameters and associated capacity
losses. For tubing requirements beyond 80 ft., substantial
capacity an d perfo rman ce losses can occu r. Fo llow ing th e
recom mend ation s in th e Lo ng line G uid eline -- R esiden tial
Split--System Air Conditioners and Heat Pumps Using Puronr
Refrigerant will reduce these losses. Refer to Table 1 for field
tubing diameters. Refer to T able 2 for accessory requirements.
There are no buried -- line applications greater than 36 in.
If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.
OUTDOOR UNIT CONNECTED TO FACTORY---AP-
PROVED INDOOR UNIT:
Outdoor unit contains correct system refrigerant charge for
operation with factory approved ARI rated indoor unit when
connected by 15 ft. of field--supplied or factory--accessory tubing,
and facto ry su p plied filter drier. C h eck refrigeran t charge for
maximum efficiency.
Table 1—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
UNIT SIZE
LIQUID
RATED VAPOR
(up to 80 ft. *)
Connection
Diameter
Tube
Diameter
Connection
Diameter
Tube
Diameter
018, 024
3/8 3/8 5/8 5/8
030, 036
3/8 3/8 3/4 3/4
042, 048
3/8 3/8 7/8 7/8
060
3/8 3/8 7/8 1 --- 1 / 8
Notes:
1. Tube diameters ar e for total equivalent len gths up to 80 ft..
2. Do not apply capillary tube or fixed orifice indoor coils to these units.
* For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (250 ft.Total Equivalent Length), refer to the Longline Guide l i n e --- A i r
Conditioners and Heat Pumps using Puron.