EasyManua.ls Logo

Carrier 24ACA - STEP 11. -Check Charge; STEP 12. -Final Checks; Installation 3

Carrier 24ACA
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9
SEQUENCE OF OPERATION
Turn on power to indoor and outdoor units. Transformer is
energized.
On a call for cooling, thermostat makes circuits R--Y and R--G.
Circuit R -- Y energizes contactor, starting outdoor fan motor and
compressor circuit. R -- G energizes indoor unit blower relay,
starting indoor blower motor on high speed.
NOTE: To achieve the rated system performance, the indoor unit
or the thermostat must be equipped with a time delay relay
circuit.
When thermostat is satisfied, its contacts open, de--energizing
contactor and blower relay. Compressor and motors stop. If
indoor unit is equipped with a time-- delay relay circuit, the indoor
blower will run an additional 90 sec to increase system efficiency.
STEP 11. Check Charge
UNIT CHARGE
Factory charge and charging method are shown on unit
information plate. Charge Puron units with cylinder in upright
po sitio n an d a co m m ercial --ty p e meterin g d ev ice in man ifo ld
hose. Charge refrigerant into suction line.
NOTE: If subcooling charging conditions are not favorable,
charge must be weighed in accordance with unit rating plate, ±0.6
oz/ft. of 3/8 -- in. liquid line above or below 15 ft., respectively.
Favorable conditions fall within the ranges given on the charging
chart on the outdoor unit plate.
NOTE: In longline applications, see Application Guideline for
special charging requirements.
EXAMPLE:
To calculate additional charge required for a 25 -- ft. line set:
25 ft. -- 15 ft. = 10 ft. X 0.6 oz/ft. = 6 oz. of additional charge.
COOLING ONLY PROCEDURE
This system requires charging by the subcooling method.
1. Operate unit a minimum of 10 minutes before checking
charge.
2. Measure liquid service valve pressure by attaching an
accurate gage to service port.
3. Measure liquid line temperature by attaching an accurate
thermistor type or electronic thermometer to liquid line
near outdoor coil.
4. Refer to unit rating plate for required subcooling
temperature.
5. Refer to Table 3. Find the point where required subcooling
temperature intersects measured liquid service valve
pressure.
6. To obtain required subcooling temperature at a specific
liquid line pressure, add refrigerant if liquid line
temperature is higher than indicated or reclaim refrigerant
if temperature is lower . Allow a tolerance of ±3_F.
STEP 12. Final Checks
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and
sheet metal edges to prevent rub-- through or wire
pinching.
2. Ensure that all wiring and tubing is secure in unit before
adding panels and covers. Securely fasten all panels and
covers.
3. Tighten service valve stem caps to 1/12--turn past finger
tight.
4. Leave Owner’s Manual with owner. Explain system
operation and periodic maintenance requirements outlined
in manual.
5. Fill out Dealer Installation Checklist and place in
customer file.
24ACA

Other manuals for Carrier 24ACA

Related product manuals