14
DETAILED COOLING CAPACITIES# (CONTINUED)
EVAPORATOR AIR
CONDENSER ENTERING AIR TEMPERATURES ° F C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM
EWB
°F(°C)
Capacity MBtuh
Tot a l
Sys.
KW**
Capacity MBtuh
Tot a l
Sys.
KW**
Capacity MBtuh
Tot a l
Sys.
KW**
Capacity MBtuh
Tot a l
Sys.
KW**
Capacity MBtuh
Tot a l
Sys.
KW**
Capacity MBtuh
Tot a l
Sys.
KW**
Tot a l Sens‡ To tal Sens‡ Tot a l Sens‡ To ta l Sens‡ To ta l Sens‡ Tota l Sens‡
24ANB160A**31 Outdoor Section W ith FE4ANB006 Indoor Section --- High
1500
57 (13.9) 52.99 52.99 3.37 51.69 51.69 3.79 50.28 50.28 4.28 48.59 48.59 4.86 46.55 46.55 5.52 44.10 44.10 6.28
62 (16.7) 55.93 48.97 3.39 54.12 48.23 3.81 52.11 47.41 4.30 49.83 46.46 4.87 47.17 45.31 5.53 44.17 44.17 6.28
63 (17.2)†† 57.08 40.23 3.40 55.22 39.43 3.82 53.16 38.56 4.31 50.77 37.56 4.88 48.01 36.42 5.54 44.77 35.10 6.29
67 (19.4) 61.59 41.74 3.45 59.56 40.94 3.86 57.29 40.06 4.35 54.69 39.06 4.92 51.67 37.92 5.58 48.16 36.60 6.34
72 (22.2) 67.81 34.35 3.51 65.53 33.47 3.92 62.98 32.51 4.41 60.07 31.43 4.98 56.73 30.22 5.65 52.84 28.84 6.41
1625
57 (13.9) 54.45 54.45 3.41 53.11 53.11 3.83 51.58 51.58 4.33 49.80 49.80 4.90 47.65 47.65 5.57 45.07 45.07 6.33
62 (16.7) 56.79 51.10 3.43 54.91 50.35 3.85 52.85 49.50 4.34 50.50 48.50 4.91 47.84 47.52 5.57 45.13 45.13 6.33
63 (17.2)†† 57.92 41.69 3.44 56.00 40.89 3.86 53.84 40.01 4.35 51.37 39.01 4.92 48.52 37.85 5.58 45.19 36.52 6.33
67 (19.4) 62.47 43.31 3.49 60.36 42.50 3.90 58.00 41.62 4.39 55.30 40.61 4.96 52.19 39.46 5.62 48.57 38.12 6.38
72 (22.2) 68.75 35.33 3.55 66.38 34.44 3.96 63.73 33.47 4.45 60.73 32.38 5.03 57.27 31.15 5.69 53.28 29.76 6.45
1750
57 (13.9) 55.78 55.78 3.46 54.36 54.36 3.88 52.76 52.76 4.37 50.87 50.87 4.95 48.62 48.62 5.62 45.94 45.94 6.38
62 (16.7) 57.54 53.15 3.47 55.63 52.37 3.89 53.51 51.48 4.38 51.15 50.35 4.95 48.69 48.69 5.62 45.99 45.99 6.38
63 (17.2)†† 58.65 43.12 3.48 56.64 42.31 3.90 54.41 41.41 4.39 51.88 40.41 4.96 48.94 39.24 5.62 45.55 37.89 6.38
67 (19.4) 63.23 44.83 3.53 61.04 44.02 3.94 58.59 43.13 4.43 55.82 42.12 5.01 52.62 40.95 5.67 48.93 39.61 6.42
72 (22.2) 69.56 36.27 3.59 67.09 35.37 4.01 64.36 34.39 4.49 61.27 33.30 5.07 57.72 32.06 5.73 53.64 30.66 6.49
2000
57 (13.9) 58.08 58.08 3.54 56.52 56.52 3.97 54.77 54.77 4.46 52.71 52.71 5.04 50.28 50.28 5.71 47.39 47.39 6.48
62 (16.7) 58.86 56.97 3.55 56.89 56.04 3.97 54.85 54.85 4.46 52.78 52.78 5.04 50.34 50.34 5.71 47.44 47.44 6.48
63 (17.2)†† 59.80 45.84 3.56 57.69 45.03 3.98 55.33 44.12 4.47 52.67 43.09 5.04 49.62 41.90 5.70 46.10 40.51 6.46
67 (19.4) 64.43 47.76 3.60 62.10 46.95 4.02 59.53 46.05 4.51 56.61 45.02 5.08 53.29 43.83 5.75 49.46 42.45 6.51
72 (22.2) 70.83 38.07 3.67 68.23 37.16 4.08 65.35 36.17 4.57 62.11 35.06 5.15 58.42 33.81 5.81 54.18 32.40 6.58
24ANB160A**31 Outdoor Section With FE4ANB006 Indoor Section --- Low
1200
57 (13.9) 40.76 40.76 2.36 37.16 37.16 2.66 33.46 33.46 2.99 29.77 29.77 3.35 26.12 26.12 3.75 22.57 22.57 4.20
62 (16.7) 42.19 38.78 2.35 38.07 35.88 2.65 33.89 32.93 2.98 29.82 29.82 3.35 26.16 26.16 3.75 22.61 22.61 4.20
63 (17.2)†† 43.06 31.53 2.35 38.84 29.02 2.65 34.53 26.48 2.98 30.23 23.96 3.35 26.04 21.51 3.75 22.00 19.12 4.20
67 (19.4) 46.64 32.86 2.32 42.08 30.29 2.62 37.46 27.69 2.96 32.85 25.12 3.33 28.35 22.61 3.74 24.02 20.17 4.19
72 (22.2) 51.58 26.79 2.29 46.57 24.53 2.59 41.50 22.25 2.93 36.46 20.00 3.30 31.55 17.82 3.71 26.80 15.71 4.17
1300
57 (13.9) 41.91 41.91 2.37 38.17 38.17 2.67 34.36 34.36 3.00 30.54 30.54 3.36 26.77 26.77 3.77 23.10 23.10 4.21
62 (16.7) 42.85 40.57 2.37 38.66 37.53 2.67 34.46 34.36 3.00 30.59 30.59 3.36 26.81 26.81 3.77 23.14 23.14 4.21
63 (17.2)†† 43.68 32.78 2.36 39.36 30.19 2.66 34.97 27.57 3.00 30.59 24.98 3.36 26.32 22.45 3.77 22.23 19.99 4.22
67 (19.4) 47.28 34.19 2.34 42.63 31.54 2.64 37.91 28.86 2.98 33.22 26.21 3.35 28.64 23.62 3.76 24.25 21.11 4.20
72 (22.2) 52.26 27.63 2.30 47.15 25.31 2.61 41.97 22.98 2.95 36.85 20.68 3.32 31.84 18.45 3.73 27.02 16.29 4.18
1400
57 (13.9) 42.94 42.94 2.39 39.09 39.09 2.68 35.16 35.16 3.01 31.22 31.22 3.38 27.35 27.35 3.78 23.58 23.58 4.23
62 (16.7) 43.45 42.26 2.38 39.24 39.02 2.68 35.21 35.21 3.01 31.27 31.27 3.38 27.39 27.39 3.78 23.62 23.62 4.23
63 (17.2)†† 44.20 33.99 2.38 39.81 31.33 2.68 35.34 28.64 3.01 30.89 25.98 3.38 26.57 23.36 3.79 22.42 20.82 4.24
67 (19.4) 47.83 35.50 2.36 43.09 32.77 2.66 38.29 30.01 2.99 33.53 27.28 3.37 28.89 24.61 3.77 24.44 22.01 4.22
72 (22.2) 52.84 28.44 2.32 47.63 26.07 2.63 42.37 23.68 2.97 37.17 21.34 3.34 32.09 19.06 3.75 27.20 16.86 4.20
1600
57 (13.9) 44.73 44.73 2.42 40.67 40.67 2.71 36.53 36.53 3.05 32.40 32.40 3.41 28.33 28.33 3.82 24.39 24.39 4.26
62 (16.7) 44.79 44.79 2.42 40.73 40.73 2.71 36.58 36.58 3.05 32.44 32.44 3.41 28.37 28.37 3.82 24.42 24.42 4.26
63 (17.2)†† 45.04 36.32 2.42 40.52 33.52 2.72 35.93 30.68 3.05 31.38 27.87 3.42 26.97 25.10 3.83 22.77 22.34 4.28
67 (19.4) 48.69 38.00 2.39 43.82 35.12 2.69 38.90 32.22 3.03 34.02 29.34 3.40 29.29 26.51 3.81 24.77 23.72 4.26
72 (22.2) 53.76 29.99 2.36 48.40 27.52 2.66 43.00 25.05 3.00 37.66 22.61 3.38 32.47 20.24 3.79 27.47 17.95 4.24
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CFM ( 480 L/S) of indoor coil air for each degree belo w 80_F(27_ C), or add 835 Btuh (245 kW) per 1000 C FM (480 L/S) of indoor coil air per degree a bove 80_F(27_C).
# Detailed cooling capacities are based on indoor and outdoor unit a t the same elevation per AHRI standard 210/240---2008. If additional tubing len gth and/or indoor un it is located above outdoor unit, a slight variation in capacity
may occur.
** System kw is total of indoor and outdoor unit kilowatts.
EWB Entering Wet Bulb
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
24ANB1