5
ELECTRICAL DATA
U n i t S i z e ---
Voltage,
Series
V/PH
OPER VOLTS* COMPR FAN
MCA
MIN
WIRE
SIZE{
MIN
WIRE
SIZE{
MAX
LENGTH
ft. (m)}
MAX
LENGTH
ft. (m)}
MAX
FUSE** or
CKT BRK
AMPS
MIN MAX LRA RLA FLA 60 C 75 C 60 C 75 C
24--- 31
208---230/1 253 197
58.3 11.1 1.8 15.7 14 14 50 (15.2) 48 (14.6) 25
36--- 31 83.0 15.3 2.0 21.1 12 12 59 (18.0) 56 (17.1) 30
48--- 31 104.0 21.2 2.7 29.2 10 10 68 (20.7) 65 ( 19.8) 40
60--- 31 152.9 28.8 2.7 38.7 8 8 80 (24.4) 76 (23.2) 60
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (NFPA 70) . The a mpacity of non ---metallic---sheathed cable (NM), trade
name ROMEX, shall be that of 60_C conditions, per th e NEC (NFPA 70) Articl e 336---26. If other than uncoated (no---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- F u l l L o a d A m p s
LRA --- L o c k e d Ro t o r A m p s
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24--- V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER (dBA)
U n i t S i z e ---
Voltage, Series
Standard Rating
(dBA)
Typical Octave Band Sp ectrum (dBA , without tone adjustment)
125 250 500 1000 2000 4000 8000
24--- 31
7 1 --- H i g h S t a g e 49.5 56.0 60.5 67.5 58.0 53.5 53.0
6 5 --- L o w S t a g e 47.0 52.0 56.5 60.5 55.0 50.0 49.0
36--- 31
6 8 --- H i g h S t a g e 47.5 53.0 60.0 60.0 56.0 52.0 51.0
6 6 --- L o w S t a g e 46.5 54.5 56.0 56.5 53.0 50.0 48.0
48--- 31
6 9 --- H i g h S t a g e 49.0 61.5 62.0 62.0 59.5 54.5 49.5
6 6 --- L o w S t a g e 48.5 59.5 59.0 59.5 56.5 51.5 48.5
60--- 31
6 9 --- H i g h S t a g e 50.8 57.5 60.5 63.0 59.5 57.5 54.5
6 8 --- L o w S t a g e 48.0 56.0 59.0 62.0 57.5 55.5 52.0
NOTE: Tested in acco r dance with AHRI Standard 270---08. (Not listed with AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE--- VOLTAGE, SERIES REQUIRED SUBCOOLING _F(_C)
24--- 31 10 (5.6)
36--- 31 11 (6.1)
48--- 31 12 (6.7)
60--- 31 14 (7.8)
ACCESSORY CONTROLS
PART NUMBER DESCRIPTION
SYSTXCCITN01 Infinity Touch Con trol (non---Wi---Fi)
SYSTXCCITW01 Infinity Touch Control with Wi---Fi & Wireless Access Point
SYSTXCC4ZC01 Infinity 4---Zone Damper Control Module (Wall ---mounted control for a four ---zone system.)
SYSTXCCSMS01 Infinity Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.)
SYSTXCCRRS01 Infinity Remote Room Sensor (Monitor s temperature in an individual zone.)
SYSTXCCRCT01 or
SYSTXCCRWF01
Infinity System Remote Access Module (Hardware for wireless access and control via internet.)
SYSTXCCNIM01 Infinity Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators on non--- zoning applications.)
24ANB1