7
Once defrost termination conditions have been met, the following
sequence will occur: The compressor will be de-- energized for
approximately 1 minute, then the reversing valve will be
de-- energized. A few seconds later, the compressor will be
re--energized and the normal heating cycle starts.
Defrost
The defrost control is a time/temperature control which has field
selectable settings of 30, 60, 90, or 120 minutes, factory set to 90
minutes. These settings represent the amount of time that must pass
after closure of the defrost thermostat before the defrost sequence
begins.
The defrost thermostat senses coil temperature throughout the
heating cycle. Wh en th e co il temp eratu re reach es the defro st
therm o stat setting o f ap proximately 3 2_F(0_C), it will close,
which energizes the DFT terminal and begins the defrost timing
sequence. When the DFT has been energized for the selected time,
the defrost cycle begins. Defrost cycle is terminated when defrost
thermostat opens, or automatically after 10 minutes.
Defrost Speedup
To initiate a forced defrost, speedup pins (J1) must be shorted with
a flat head screwdriver for 5 seconds and RELEASED.Ifthe
defrost thermostat is open, a short defrost cycle will be observed
(actual length depends on Quiet Shift-- 2 switch position). When
Quiet Shift-- 2 is off, only a short 30 second defrost cycle is
observed. With Quiet Shift-- 2 ON, the speedup sequence is
approximately 3 minutes; 1 minute compressor off period followed
by 30 seconds of defrost with compressor operation. When
returning to heating mode, the compressor will turn off for an
additional 1 minute.
If the d efrost th ermostat is clo sed , a co m p lete defrost cycle is
initiated. If the Quiet Shift--2 switch is turned on, the compressor
will be turned off for two 1 minute intervals as explained
previously.
OF2
O
F1
ON
QUIET
SHIFT
120
30
60
60
30
90
INTERVAL TIMER
OFF
P3
DFT
O R W
2
Y C
T2 C C O
DFT
T1 Y
P1
J1
SPEEDUP
A05378
Fig. 11 Defrost Control HK32EA008
A170130
Fig. 12 Defrost Control HK32EA010
Table 4 Defrost Control Speedup–Timing Sequence
PARAMETER
MINIMUM
(MINUTES)
MAXIMUM
(MINUTES)
SPEEDUP
(NOMINAL)
30–minute cycle 27 33 7sec
50–minute cycle 45 55 12 sec
90–minute cycle 81 99 21 sec
10–minute cycle 9 11 2sec
5 minutes 4.5 5.5 1sec