Table 15 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
OPT2
ENTER
CTRL X CONTROL METHOD Default: 0
0 = Switch
1 = 7 Day Schedule
2 = Occupancy
3 = CCN Control
CCNA XXX CCN ADDRESS Default: 1
Range: 1 to 239
CCNB XXX CCN BUS NUMBER
Default: 0
Range: 0 to 239
BAUD X CCN BAUD RATE Default: 3
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
LOAD X LOADING SEQUENCE SELECT Default: 1
1 = Equal
2 = Staged
LLCS X LEAD/LAG CIRCUIT SELECT Default: 1 (size 080-420) 2 (size 040-070)
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
LCWT XX.X DF HIGH LCW ALERT LIMIT Default: 60
Range: 2 to 60 F
DELY XX MIN MINUTES OFF TIME Default: 0 Minutes
Range: 0 to 15 Minutes
RSET
ENTER
CRST X COOLING RESET TYPE 0 = No Reset
1=4to20mAInput
2 = Outdoor Air Temperature
3 = Return Fluid
4 = Space Temperature
CRT1 XXX.X °F NO COOL RESET TEMP Default: 125 F
Range: 0 to 125 F
CRT2 XXX.X °F FULL COOL RESET TEMP Default: 0° F
Range: 0 to 125 F
DGRC XX.X DF DEGREES COOL RESET Default: 0° F
Range: −30 to 30 F
DMDC X DEMAND LIMIT SELECT Default: 0
0 = None
1 = Switch
2=4to20mAInput
3 = CCN Loadshed
DM20 XXX % DEMAND LIMIT AT 20 MA Default: 100%
Range: 0 to 100%
SHNM XXX LOADSHED GROUP NUMBER Default: 0
Range: 0 to 99
SHDL XXX % LOADSHED DEMAND DELTA Default: 0%
Range: 0 to 60%
SHTM XXX MIN MAXIMUM LOADSHED TIME Default: 60 minutes
Range: 0 to 120 minutes
DLS1 XXX % DEMAND LIMIT SWITCH 1 Default: 80%
Range: 0 to 100%
DLS2 XXX % DEMAND LIMIT SWITCH 2 Default: 50%
Range: 0 to 100%
LLEN ENBL/DSBL LEAD/LAG CHILLER ENABLE Default: Disable
MSSL SLVE/MAST MASTER/SLAVE SELECT Default: Master
SLVA XXX SLAVE ADDRESS Default: 0
Range: 0 to 239
LLBL ENBL/DSBL LEAD/LAG BALANCE SELECT Default: Disable
LLBD XXX HRS LEAD/LAG BALANCE DELTA Default: 168 hours
Range: 40 to 400 Hours
LLDY XX MIN LAG START DELAY
Default: 5 minutes
Range: 0 to 30 minutes
SLCT
ENTER
CLSP X COOLING SETPOINT SELECT Default: 0
0 = Single
1 = Dual Switch
2 = Dual Clock
3=4to20mAInput
RL.S ENBL/DSBL RAMP LOAD SELECT Default: Enable
CRMP X.X COOLING RAMP LOADING Default: 1.0
Range: 0.2 to 2.0
Z.GN X.X DEADBAND MULTIPLIER Default: 1.0
Range: 1.0 to 4.0