Table 17 — Example of Configuring Dual Chiller Control
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
RSET
ENTER
CRST 0
LLDY 5 LAG START DELAY
ENTER
5 Scrolling stops
ENTER
5 Value flashes
10 Select 10
ENTER
10 Change accepted
ESCAPE
LLDY 10
LLBD 168 LEAD/LAG BALANCE DELTA No change needed. Default set for weekly changeover
LLBL DSBL LEAD/LAG BALANCE SELECT
ENTER
DSBL Scrolling stops
ENTER
DSBL Value flashes
ENBL Select Enable
ENTER
ENBL Change accepted
ESCAPE
LLBL ENBL
SLVA 0 SLAVE ADDRESS
ENTER
0 Scrolling stops
ENTER
0 Value flashes
6 Select 6
ENTER
6 Change accepted
ESCAPE
SLVA 6
MSSL MAST MASTER/SLAVE SELECT No change needed. Default set for Master
LLEN DSBL LEAD/LAG CHILLER ENABLE
ENTER
DSBL Scrolling stops
ENTER
DSBL Value flashes
MAST Select Master
ENTER
LLEN MAST Change accepted
ESCAPE
LLEN MAST LEAD/LAG CHILLER ENABLE Item/Value/Units scrolls again
39