CONFIGURATION SCREEN (TYPE 10)
OPTIONS2 (Options Configuration)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Control Method 0 = Switch
1 = 7 day sched.
2 = Occupancy
3 = CCN
0 CONTROL
2 Loading Sequence Select 1 = Equal loading
2 = Staged loading
1 SEQ TYPE
3 Lead/Lag Sequence Select 1 = Automatic
2 = Circuit A leads
3 = Circuit B leads
1 LEAD TYP
4 Cooling Setpoint Select 0 = Single
1 = Dual, remote switch controlled
2 = Dual, clock controlled
3 = 4-20 ma input
0 CLSP TYP
5 Ramp Load Select ON/OFF OFF RAMP EBL
6 High LCW Alert Limit 2 to 60 60.0 ^F LCW LMT
7 Minutes off time 0 to 15 0 min DELAY
8 Deadband Multiplier 1.0 to 4.0 1.0 Z GAIN
DISPLAY (STDU SETUP)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 STDU Password nnnn 1111 PASSWORD
2 Password Enable enable/disable enable PASS EBL
3 Metric Display Off/On Off DISPUNIT
4 Language 0 = ENGLISH
1 = FRANCAIS
2 = ESPANOL
3 = PORTUGUES
0 LANGUAGE
CONFIG (TIMED OVERRIDE SETUP)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Schedule Number 0-99 0 SCHEDNUM
2 Override Time Limit 0-4 0 hours OTL
3 Timed Override Hours 0-4 0 hours OTL EXT
ALARMDEF (Alarm Definition Table)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Alarm Routing Control
ALRM_CNT
00000000 00000000
2 Equipment Priority
EQP_TYPE
0to7 4
3 Comm Failure Retry Time 1 to 240 10 min RETRY_TM
4 Re-alarm Time 1 to 255 30 min RE-ALARM
5 Alarm System Name XXXXXXXX 30_PIC ALRM_NAM