RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 COOLING RESET
2 Cooling Reset Type 0 = No Reset
1 = 4-20 ma input
2 = External temp-OAT
3 = Return fluid
4 = External temp-SPT
0 CRST TYP
3 No Cool Reset Temp 0 to 125 0.0 °F CT NO
4 Full Cool Reset Temp 0 to 125 125.0 °F CT FULL
5 Degrees Cool Reset −30 to 30 0.0 ^F CT DEG
6 DEMAND LIMIT
7 Demand Limit Select 0 = None
1 = External switch input
2 = 4-20 ma input
3 = Loadshed
0 DMD CTRL
8 Demand Limit at 20mA 0 to 100 100 % DMT20MA
9 Loadshed Group Number 0 to 99 0 SHED NUM
10 Loadshed Demand Delta 0 to 60 0 % SHED DEL
11 Maximum Loadshed Time 0 to 120 60 min SHED TIM
12 Demand Limit Switch 1 0 to 100 80 % DLSWSP1
13 Demand Limit Switch 2 0 to 100 50 % DLSWSP2
14 LEAD/LAG
15 Lead/Lag Enable Enable/Disable Disable LL ENA
16 Master/Slave Select Slave/Master Master MS SEL
17 Slave Address 0 to 239 0 SLV ADDR
18 Lead/Lag Balance Select Enable/Disable Disable LL BAL
19 Lead/Lag Balance Delta 40 to 400 168 hours LL BAL D
20 Lag Start Delay 0 to 30 5 mins LL DELAY
BRODEFS (Broadcast POC Definition Table)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 CCN Time/Date Broadcast Yes/No No CCNBC
2 CCN OAT Broadcast Yes/No No OATBC
3 Global Schedule Broadcst Yes/No No GSBC
4 CCN Broadcast Acker Yes/No No CCNBCACK
5 Daylight Savings Start
6 Month 1 to 12 1 STARTM
7 Week 1to5 1 STARTW
8 Day 1to7 0 STARTD
9 Minutes to add 0 to 99 0 min MINADD
10 Daylight Savings Stop
11 Month 1 to 12 1 STOPM
12 Week 1 to 5 1 STOPW
13 Day 1 to 7 0 STOPD
14 Minutes to subtract 0 to 99 0 min MINSUB