CURRMODS
DESCRIPTION STATUS UNITS POINT
1 FSM controlling chiller ON/OFF MODE 1
2 WSM controlling chiller ON/OFF MODE 2
3 Master/Slave control ON/OFF MODE 3
4 Low source protection ON/OFF MODE 4
5 Ramp Load Limited ON/OFF MODE 5
6 Timed Override in effect ON/OFF MODE 6
7 Low Cooler Suction TempA ON/OFF MODE 7
8 Low Cooler Suction TempB ON/OFF MODE 8
9 Slow Change Override ON/OFF MODE 9
10 Minimum OFF Time ON/OFF MODE 10
11 Low Suction Superheat A ON/OFF MODE 11
12 Low Suction Superheat B ON/OFF MODE 12
13 Dual Setpoint ON/OFF MODE 13
14 Temperature Reset ON/OFF MODE 14
15 Demand Limit in effect ON/OFF MODE 15
16 Cooler Freeze Prevention ON/OFF MODE 16
17 Lo Tmp Cool/Hi Tmp Heat ON/OFF MODE 17
18 Hi Tmp Cool/Lo Tmp Heat ON/OFF MODE 18
SETPOINT
DESCRIPTION STATUS UNITS POINT DEFAULTS
1 COOLING
2 Cool Setpoint 1 −20 to 70 °F CSP1 44
3 Cool Setpoint 2 −20 to 70 °F CSP2 44
4 RAMP LOADING
5 Cooling Ramp Loading 0.2 to 2.0 °F/min CRAMP 1.0
6 HEAD PRESSURE
7 Head Press. Stpt A 80 to 140 °F HSP A
113
8 Head Press. Stpt B 80 to 140 °F HSP B
113
LID DEFAULT SCREEN DEFINITION
TABLE TYPE 19 HEX
DESCRIPTION STATUS UNITS POINT DISPLAY
1 (SYSTEM PRIMARY MESSAGE)
2 (SYSTEM SECONDARY MESSAGE)
3 Machine Operating Hours nnnnn hours HR MACH
HR MACH
4 Entering Chilled Water snnn.n °F EWT EWT
5 Leaving Chilled Water snnn.n °F LWT LWT
6 Control Point snnn.n °F CTRL PNT
CTRL PNT
7 Percent Total Capacity 0-100 % CAP T CAP T
8 Active Demand Limit 0-100 % DEM_LIM DEM_LIM
9 Operating Setpoint snnn.n °F SP SP
10 Circuit A Total Cap 0-100 % CAPA T
CAPA T
11 Circuit B Total Cap 0-100 % CAPB T CAPB T
12 Machine Starts nnnnn CY MACH CY MACH
73