CSM/FSM EQUIPMENT TABLE (Type 621H, Block 2)
LINE DESCRIPTION POINT
1 Chiller Status
0 = Chiller is off
1 = Valid run state in CCN mode
2 = Recycle active
3 = Chiller is in Local Mode
4 = Power Fail Restart in Progress
5 = Shutdown due to fault
6 = Communication Failure
CHILSTAT
2 unused
3 Percent Total Capacity Running CAP T
4 Service Runtime HR MACH
5 unused
6 unused
7 unused
8 Power Fail Auto Restart ASTART
9 Percent Available Capacity On CAP A
WSM EQUIPMENT PART COOL SOURCE MAINTENANCE TABLE
SUPERVISOR MAINTENANCE TABLE
DESCRIPTION STATUS POINT
WSM Active? Yes WSMSTAT
Chilled water temp 46.5 °F CHWTEMP
Equipment status On CHLRST
Commanded state Enable/Disable/None CHLRENA
CHW setpoint reset value 2.0 ^F CHWRVAL
Current CHW setpoint 44.0 °F CHWSTPT
OCCUPANCY MAINTENANCE TABLE
OCCUPANCY SUPERVISORY
DESCRIPTION STATUS POINT
Current Mode (1=Occup.) 0,1 MODE
Current Occup. Period # 0-8 PER-NO
Timed-Override in Effect Yes/No OVERLAST
Time-Override Duration 0-4 hours OVR HRS
Current Occupied Time 0:00 STRTTIME
Current Unoccupied Time 0:00 ENDTIME
Next Occupied Day NXTOCDAY
Next Occupied Time 0:00 NXTOCTIM
Next Unoccupied Day NXTUNDAY
Next Unoccupied Time 0:00 NXTUNTIM
Previous Unoccupied Day PRVUNDAY
Previous Unoccupied Time 0:00 PRVUNTIM