12.2.3.3 - Installation
The hydraulic supply for each desuperheater is delivered in
parallel.
The hydraulic connection on the desuperheater water inlet and
outlets must not generate any local mechanical stress on the
exchangers. If necessary, install exible couplings.
Fit water ow rate balancing and control valves at the exchanger 
outlet.
Balancing  and  control  of  the  ow  rates  may  be  performed  by 
reading the pressure drop in the exchangers.
The pressure drop on each of these must be identical to the total
water ow rate given by the selection programme.
To adjust the balancing valves before starting up the system, refer
to the pressure drop curves below.
It  is  possible  to  ne-tune  the  water  ow  rate  settings  for  each 
desuperheater when the unit is running at full load by trying to
obtain water outlet temperatures which are strictly identical for
each of the circuits.
Desuperheater (plate heat exchanger pressure drop curves)
1
10
100
0,11 10 100
1 2 3 4
5 6
Heat exchanger pressure drop (kPa)
Heat exchanger water ow rate (l/s)
1 Circuit with 1 compressor (165-550 KW units) 4 Circuit with 4 compressors (165-550 KW units)
2 Circuit with 2 compressors (165-550 KW units) 5 Circuit with 3 compressors (610-850 KW units)
3 Circuit with 3 compressors (165-550 KW units) 6 Circuit with 4 compressors (610-850 KW units)
12.2.3.4 - Operation
The desuperheater water circuit pump (see standard diagram – 
item 20, in the section on "Installation and operation of the heat
recovery  with  desuperheater  option")  can  be  operated  in
conjunction with:
- Start-up of the rst unit compressor: terminal 37/38
- Heating water requirement: output DO-01, terminal 491/492,
on the EMM board.
Adedicated ow switch (item 29) can also be installed to generate 
an alarm if there is a problem with the pump (customer control 
system).
The volume of the desuperheater circuit water loop must be as
low as possible to be able to rapidly increase the temperature
during warm-up.
The minimum desuperheater water inlet temperature is 30 °C.
This may require the use of a three-way valve (item 31), with its 
controller and sensor controlling the minimum required water inlet
temperature.
It is essential for the desuperheater water loop to comprise a valve
and an expansion vessel which must be selected to take the
volume of the water loop and the maximum possible temperature
into  account  (120  °C),  in  the  event  that  pump  (item  20)  stops 
running.
12.2.3.5 - Operating limits
30RB/RBP 170-950 units
Desuperheater Minimum Maximum
Water inlet temperature at start-up °C 30
(1)
75
Water outlet temperature during operation °C 45 80
Water inlet temperature on shut-down °C 3 75
30RQ/RQP 165-520 units
Desuperheater Minimum Maximum
Water inlet temperature at start-up °C 30
(1)
60
Water outlet temperature during operation °C 45 80
Water inlet temperature on shut-down °C 3 60
Note: Do not exceed the maximum operating temperature.
(1)   On start-up, the water  inlet  temperature  must  not be below 25 °C. On lower 
temperature installations, a 3-way valve is required until the desuperheater water
outlet reaches 45 °C.