12.2.4 - TOTAL HEAT RECOVERY (option 50)
Suitable for heating, domestic hot water production, agriculture and food industry, industrial processes and other hot-water requirements.
With the total heat recovery option it is possible to reduce the energy consumption bill considerably, when compared to conventional
heating equipment such as fossil fuel boilers or electric water tanks.
Operating principle
If hot water production is required, the compressor discharge gases are directed towards the heat recovery condenser. The refrigerant
releases its heat to the hot water that leaves the condenser at a temperature of up to 60 °C. In this way, 100% of the heat rejected by 
the liquid chiller can be used to produce hot water. The hot water temperature is controlled by the chiller's SmartVu
TM
control unit
NOTE: Heat recovery is only possible if the unit is producing cooling at the same time.
12.2.4.1 - Physical properties of units with total heat recovery
30RBP 170R 190R 210R 230R 270R 310R 340R 380R 410R 450R
Total recovery exchanger Brazed-plate heat exchanger
Water volume circuits A/B l 20 24 24 29 29 31 31 31 31 44
Maximum operating pressure, water side kPa 600 600 600 600 600 600 600 600 600 600
Hydraulic connections Victaulic
Connection in 3" 3" 3" 3" 3" 4" 4" 4" 4" 4"
External diameter mm 88,9 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3 114,3
Operating weight
(1)
Standard unit + total recovery option kg 1490 1580 1580 1740 1775 2300 2354 4561 2620 3084
Unit with option 15LS + total recovery option
(2)
kg 1573 1663 1663 1849 1884 2427 2481 4706 2765 3247
Refrigerant
(3) (4)
R32 / A2L / GWP=675 as per AR4
Circuit A
kg 11,5 13,7 13,7 19,3 19,7 20,0 20,8 28,7 29,3 30,4
tCO
2
e 7,8 9,2 9,2 13,0 13,3 13,5 14,0 19,4 19,8 20,5
Circuit B
kg 16,2 19,2 19,2 19,3 19,7 28,1 28,9 28,7 29,3 33,0
tCO
2
e 10,9 13,0 13,0 13,0 13,3 19,0 19,5 19,4 19,8 22,3
30RBP 480R 550R 610R 670R 720R 770R 800R 870R 950R
Total recovery exchanger Brazed-plate heat exchanger
Water volume circuits A/B l 44 44 61 61 61 61 61 61 61
Maximum operating pressure, water side kPa 600 600 600 600 600 600 600 600 600
Hydraulic connections Victaulic
Connection in 4" 4" 5" 5" 5" 5" 5" 5" 5"
External diameter mm 114,3 114,3 139,7 139,7 139,7 139,7 139,7 139,7 139,7
Operating weight
(1)
Standard unit + total recovery option kg 3110 3315 3848 4093 4093 4627 4627 4876 4876
Unit with option 15LS + total recovery option
(2)
kg 3273 3496 3981 4246 4246 4801 4801 5070 5070
Refrigerant
(3) (4)
R32 / A2L / GWP=675 as per AR4
Circuit A
kg 30,7 33,9 41,8 43,2 43,2 44,7 44,7 50,9 50,9
tCO
2
e 20,7 22,8 28,2 29,2 29,2 30,2 30,2 34,3 34,3
Circuit B
kg 33,4 33,9 43,2 43,2 43,2 50,9 50,9 50,9 50,9
tCO
2
e 22,5 22,8 29,2 29,2 29,2 34,3 34,3 34,3 34,3
(1)   Weights are guidelines only. Refer to the unit name plate.
(2)  Options: 15LS = Very low sound level, 
(3)  Values are guidelines only. Refer to the unit name plate.
(4)  For a combination of option 50 and 6B, refer to the unit name plate
12 - OPTIONS
63