The following list describes the possible cause for each alarm code:
Diagnostic
The electronic control on the machine continuously 
monitors its operation. In the event of a malfunction, it 
activates a relay whose contact generates a coded alarm 
TJHOBMTFOEJOH0/0''TJHOBMTUPUIFSFNPUFDPOUSPMBOE
switching on the alarm LED. 
Some alarm conditions are automatically reset, others 
require the intervention of the operator to search for the 
GBVMUSFNPWFJUTDBVTFBOETXJUDIUIFVOJUCBDLPO
.BOVBMSFTFUUJOHPGBMBSNDPOEJUJPOT
Manual resetting of alarm conditions is performed using the
SFNPUF0/0''CVUUPOCZTJNQMZTXJUDIJOH0''BOEUIFO
0/BHBJO
or opening and closing S1 switch (see electrical 
connections page 10).
WARNING: NBOVBMSFTFUUJOHDBVTFTUIFEFöOJUJWFMPTTPG
UIFBMBSNDPEFUIFSFGPSFCFGPSFBNBOVBMSFTFUDIFDLUIF
code according to the instruction reported and remove its 
cause.
/#5FNQPSBSZQPXFSTVQQMZGBJMVSFUPBVOJUJOBOBMBSN
condition does not reset the unit.
"MBSNDPEJöDBUJPO
The alarm code generated by a failure, is shown to the 
operator one time only, and the unit remains in alarm status. 
To have the alarm code shown again, press the ECO button 
"MBSNDPEFXJUIQFSTJTUFOUBMBSNDPOEJUJPO
    LED on for 1 second
 
  LED o for 1 second
To have the alarm code shown again, press the ECO button 
on the remote control.
#ZQSFTTJOHUIF0/0''CVUUPOUIFVOJUJTUVSOFEOFF and 
the alarm code is shown again. To restart the unit, remove 
UIFBMBSNDBVTFBOEQSFTTUIF0/0''CVUUPOBHBJO
1 + 1 + 1=3 1
31
on the remote control.
5IFBMBSNDPEJöDBUJPOJTCBTFEPOUIFCJOBSZUXPEJHJUDPEF
X1 and X2, as follows:
UIFöSTUöHVSF9øBTIFTBUTFDPOEJOUFSWBMTVOUJMJU
SFBDIFTUIFOVNCFSDPSSFTQPOEJOHUPUIFöSTUEJHJUBGUFSB
QBVTFPGTFDPOETTFDPOEöHVSF9TUBSUTUPøBTIBHBJO
with 1 second intervals until the number corresponding to 
the second is reached (only for two-digit codes).
"MBSN Description
Control 
action
"MBSN
reset 
NFUIPE
1SPCBCMFDBVTF
1 Compressor fault
Compressor 
stopped
Manual Compressor overheated
2
Leaving water temperature 
probe fault
Unit 
stopped
Automatic
Sensor out of range, probe wire interruption or 
sensor fault
3
Entering water temperature 
probe fault
Unit 
stopped
Automatic
Sensor out of range, probe wire interruption or 
sensor fault
5 Air temperature probe fault
Unit 
stopped
Automatic
Sensor out of range, probe wire interruption or 
sensor fault
6 High pressure transducer fault
Unit 
stopped
Automatic
Transducer out of range, incorrect transducer 
voltage transducer wire interrupted or transducer 
fault
11 Low pressure transducer fault
Unit 
stopped
Automatic
Transducer out of range, incorrect transducer 
voltage transducer wire interrupted or transducer 
fault
13
Low refrigerant pressure in the 
circuit
Unit 
stopped
Automatic/
Manual
-BDLPGSFGSJHFSBOUJOUIFDJSDVJUCMPDLFE
SFGSJHFSBOUöMUFSPSMPXQSFTTVSFUSBOTEVDFSGBVMU
14
High refrigerant pressure in the 
circuit
Unit 
stopped
Manual
Fan fault, coil obstructed, high outdoor air 
temperature
15
High pressure safety switch / 
reverse compressor rotation
Unit 
stopped
Manual
The safety pressure switch has not been reset after 
the last alarm, incorrect compressor connection
16
1MBUFFYDIBOHFSBOUJGSFF[F
protection
Unit 
stopped
Automatic/
Manual
Low water ow rate entering or leaving water 
probe fault
21
Repeated attainment of low 
suction temperature in cooling 
(more than six times)
Unit 
stopped
Automatic
-PXQSFTTVSFUSBOTEVDFSGBVMUPSMBDLPGSFGSJHFSBOU
in the circuit
22
Repeated attainment of high 
pressure condition in cooling 
(more than six times)
Unit 
stopped
Automatic
High pressure transducer fault high air 
temperature, high entering water temperature
26 0VUEPPSJOUFSCMPDLGBVMU
Unit 
stopped
Manual Flowswitch tripped or fault, air in the water circuit
33 Maintenance service request
Unit 
stopped
Manual -