Service manual
22
defrosting mode or the end of defrost.
8.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes after
starting and then judge temperature. Meanwhile other protections are still valid.
* This parameter can be changed from 0 to 3
8.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function
prevails.
Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
8.8.5 Auto wind at heating mode (T=indoor temp.)
8.8.6 Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)