Carrier 38AD - Thermostatic Expansion Valve Installation; Suction Piping and TXV Bulb Location; Unit Safety Relief System; Wiring and Electrical Data Overview

Carrier 38AD
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig.
9
Recommended
Filter-Drier(s)
and
Sight
Glass
Locations
Table
5
Filter-Drier
Replacement
Parts
and
Data
UNIT
FILTER-DRIER
Part
No.
Qty
Conn.
Size
;
Replacement
Part
No.
Core
Qty
38AD024
KH43LE1
23
1
%
:
Same
0
38AD028
|
KH43LE121
2
s
Same
0
38AD034
j
KH43LE
121
2
%
Same
0
38AD044
j
KH49EA030
1
X
KH29EZ050*
2
38AB054
!
KH49EA120
1
l
1
/*
KH29EZ050*
2
38AB064
|
KH49EA120
1
i
l
/
8
KH29EZ050*
2
38AB084
KH49EA040
1
iv»
KH29EZ050*
3
*
Replaceable
cores
only
Install
field-supplied
thermostatic
expansion
valve
in
liquid
line
ahead
of
each
evaporator
section.
For
two-step
cooling,
the
solenoids
used
must
be
wired
to
be
opened
by
control
from
a
two-step
thermostat
For
example:
two
solenoids
may
be
used
with
three
TXV’s
one
of
the
solenoids
serving
a
liquid
line
feeding
two
of
the
TXV’s.
When
three
solenoids
are
used
with
three
TXV’s,
two
of
the
solenoids
must
be
tied
in
parallel
with
the
thermo¬
stat
to
serve
the
one
liquid
line
feeding
the
two
TXV’s.
The
third
solenoid
operates
independently
for
the
other
step
of
cooling.
Suction
Piping
at
Evaporator
and
TXV
Bulb
Location
The
purpose
of
these
recommendations
is
to
achieve
good
mixing
of
the
refrigerant
leaving
the
evaporator
suction
header
for
proper
sensing
by
the
TXV
bulb.
1.
A
minimum
of
two
90°
elbows
must
be
installed
upstream
of
the
expansion
valve
bulb
location.
2.
The
thermal
bulb
must
be
strapped
to
a
vertical
riser
following
the
second
elbow
of
item
1.
This
riser
must
be
at
least
15
pipe
diameters
high
and
the
bulb
should
be
fastened
10
pipe
diameters
above
the
preceding
elbow.
3.
S
i
ze
the
suction
line
from
near
evaporator
thru
the
15
diameter
long
riser
for
high
velocity.
Enter
the
suction
pipe
sizing
charts
in
Carrier
System
Design
Manual
at
corrected
design
tons
(each
evaporator
split)
and
80
feet
equivalent
length
(for
loss).
Choose
the
smaller
size
pipe,
when
reading
falls
between
two
sizes
on
chart.
Since
the
selection
of
suction
piping
recommended
for
high
velocity
is
approxi¬
mately
20
ft
equivalent
length,
this
sizing
method
will
result
in
about
0.5°
friction
loss
for
that
section.
If
a
loss
is
allowed
for
the
entire
suction
line,
this
leaves
1.5°
tor
the
balance
of
suction
line
and
should
be
sized
on
that
basis.
This
high-velocity
sizing
should
be
adequate
for
oil
return
up
the
15
diameter
long
riser.
It
should
be
checked.
If
an
oil
return
connection
at
the
bottom
of
the
suction
header
is
supplied
with
an
evaporator,
this
connection
must
be
teed
in
ahead
of
first
mixing
elbow
(Fig.
8).
When
the
compressor
is
below
the
evaporator,
the
riser
at
the
evaporator
does
not
have
to
extend
as
high
as
the
top
level.
After
the
15
diameter
riser
has
been
provided,
the
suction
may
elbow
down
immediately.
Safety
Relief
A
fusible
plug
is
located
on
unit
liquid
line
before
liquid
valve.
WIRING
AND
ELECTRICAL
DATA
Power
Supply
Electrical
characteristics
of
avail¬
able
power
supply
must
agree
with
unit
nameplate
rating.
Supply
voltage
must
be
within
tolerances
shown
in
Table
6.
Phase
unbalance
must
not
exceed
2%.
Operation
of
unit
on
improper
supply
voltage
or
with
excessive
phase
unbalance
con¬
stitutes
abuse
and
is
not
covered
by
Carrier
Warranty.
Power
Wiring
All
power
wiring
must
comply
with
applicable
local
and
national
codes.
Install
a
field-supplied
branch
circuit
disconnect
switch
of
a
type
that
can
be
locked
“Off’
or
“Open.”
Run
power
wires
from
the
disconnect
switch
thru
the
power
opening
(H
on
Fig.
1)
on
unit
and
connect
to
terminal
block
just
inside
the
opening.
On
38AB084,
there
are
two
terminal
blocks
(on
208-volt
and
230-volt
units
only).
Each
is
limited
to
350
MCM
maximum
wire
size
(see
Table
7).
These
units
are
provided
with
two
power
openings
to
accommodate
two
conduit
runs.
For
access
to
power
opening
and
terminal
blocks
on
38AD044,
unlatch
the
two
latches
on
the
outer
hinged
door
and
swing
open
outer
door.
Remove
screws
on
barrier
panel
and
remove
barrier
to
expose
wiring.
5