Carrier 38AD - Refrigerant Piping Guidelines; Refrigerant Line Sizing; Single Pumpout Control Setup; Refrigerant Drier & Moisture Indicator

Carrier 38AD
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FROM
FAN
CONTACTOR
200,
208,
230
OR
460
VOLTS
200,
208-,
AND
230-VOLT
UNITS
.^ffV
vBRN
a
BRN.
MOTOR
SUITABLE
FOR
USE
WITH
32LT
'MOTORMASTER
SPEED
CONTROLLER*
200-,
230“V
RATED
CONTROLLER
*Use
230-volt
controller
with
200-,208-
or
230-volt
motors
Fig.
7
Motormaster®
Electrical
Connections
Table
4
Components
Required
for
MOTORMASTER
Use
UNIT
MODEL
RUN
CAPACITOR
TRANS¬
FORMER
MOTOR
38AD024
600
100
HC96LH020
HT01AH951
HT01AH959
HC46VL220
or
HC46VL221
38AD028
38AD034
38AD044
38AB054
38AB064
38AB084
600
HC96LH030
HT01AH952
HC52TE230
100
HT01AH954
REFRIGERANT
PIPING
Refrigerant
Line
Sizes
will
depend
on
length
of
piping
required
between
condensing
unit
and
evap¬
orator.
Consideration
must
be
given
to
liquid
lift
and
to
compressor
oil
return.
Refer
to
Part
3
of
Carrier
System
Design
Manual
for
line
sizing
information
and
Fig.
8
for
recommended
piping
details.
Single
Pumpout
Control
All
units
are
factory
wired
to
operate
on
single
pumpout
control
and
require
a
field-supplied
liquid
line
solenoid
valve,
sized
for
minimum
pressure
drop,
to
be
installed
immediately
ahead
of
each
expansion
valve.
If
unit
is
to
be
used
with
a
chiller,
wiring
modifications
may
be
necessary.
Refer
to
38AB
Application
Data,
Chilled
Water
Applications.
Refrigerant
Drier
and
Moisture
Indicator
A
filter-drier(s)
and
a
liquid-moisture
indicator
are
shipped
with
unit
for
field
installation.
Refer
to
Fig.
9
for
typical
recommended
piping
arrange¬
ments
and
to
Table
5
for
physical
data
on
driers.
Receiver
No
receiver
is
provided
with
unit.
It
is
recommended
that
one
not
be
used.
Piping
Procedure
Do
not
remove
plastic
dust
plugs
from
suction
and
liquid
line
stubs
in
com¬
pressor
compartment
until
piping
connections
are
ready
to
be
made.
Pass
nitrogen
or
other
inert
gas
thru
piping
while
brazing,
to
prevent
formation
of
copper
oxide.
NOTES
2
D
as
used
in
8D
etc,
indicates
the
pipe
diameter
size
as
a
measure
of
length
1
Lower
split
first
on,
last
off
3
TXVE
indicates
Thermostatic
Expansion
Valve
Equalizer
Connection
Fig.
8
Typical
Piping
Connections
for
Face
Split
Coils
77
7
4