EasyManua.ls Logo

Carrier 38AD - Remote Control Wiring Options; Line Voltage Remote Control Setup; Low-Voltage Remote Control Setup; Unit Start-Up Procedures

Carrier 38AD
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
7
—
Maximum
Field
Wire
Sizes
UNIT
SIZE
VOLTS
(60-Hz)
WIRE
SIZE
CONN.
38AD
024,028/034
208
230
6
AWG
to
350
MCM
TB
460
575
14
AWG
to
2/0
044
460
575
208
230
6
AWG
to
350
MCM
I
TB
CT
38AB
054,064
208
230
6
AWG
to
350
MCM
CT
460
575
6
AWG
to
3/0
084
All
6
AWG
to
350
MCM
CT
CT
-
Compression
Terminal
(attached
to
terminal
block)
TB
—
Terminal
Block
(with
integral
compression
terminal)
TB
DT---
0
---
0
--
-
0
---
0
0
-
-T
I
-I
-
I
_-4
TC|
TC;2*^0-
'i
s,
fea-
--
L
-
2
%X3
TWO
STEP
COOLING
38AB054,
064
AND
084
_I
LEGEND
CR
—
Control
Relay
TC
—
Thermostat,
Cooling
LLS
—
Liquid
Line
Solenoid
-Field
Wiring
TB
—
Terminal
Board
(at
unit)
*Field
Supplied
Fig.
10
—
Control
Circuit
Wiring
with
Line
Voltage
(115,
208-
or
230-volt)
Thermostat
LINE
VOLTAGE
REMOTE
CONTROL
-
Install
field-supplied
line
voltage
thermostat(s)
as
shown
in
Fig.
10
for
two-step
cooling.
Wire
liquid
line
solenoid
as
shown.
LOW-VOLTAGE
REMOTE
CONTROL
-
Install
field-supplied
accessories
as
shown
in
Fig.
11
or
Fig.
12
for
either
two-step
cooling
or
two-step
cooling,
one-step
heating.
Wire
liquid
line
solenoids
as
shown.
START-UP
Preliminary
Checks
->
1.
Compressor
oil
level
must
be
visible
at
sight
glass
in
each
compressor
crankcase.
Add
oil
if
necessary.
2.
Each
compressor
must
float
freely
on
its
mounting
springs.
3.
All
internal
wiring
connections
must
be
tight,
and
all
barriers
and
covers
must
be
in
place.
->
Toggle
switches
for
units
38AB054,064
and
084
must
be
in
“On”
position.
4.
Electrical
power
source
must
agree
with
unit
nameplate
rating.
5.
All
service
valves
must
be
open.
6.
Fan
cycling
thermostat
sensing
bulb
must
be
in
air
stream
under
fan
no.
1.
7.
Crankcase
heater
must
be
firmly
locked
into
the
compressor
crankcase.
Leak
Test
the
entire
refrigerant
system
by
the
Pressure
Method
described
in
the
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Section
1-6.
Use
R-22
at
approximately
25
psig
backed
up
with
an
inert
gas
to
a
total
pressure
not
to
exceed
245
psig.
Evacuate
and
Dehydrate
the
entire
refrigerant
system
by
either
of
the
methods
described
in
the
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Section
1-7.
Li
38A
B
,
0
5
4,0
6
4,
084,
SDRl
>-2l
(IMS)
-
SR|
—'
p-6
i(0-OH-
l
ONE
“
STEP
HEATING
CONTROLS
THERMOSTAT
HH07AT072
SUBBASE
HH93AZ080
LEGEND
AHA
—
Adjustable
Heat
Anticipator
CC
—
Cooling
Compensator
CR
—
Control
Relay
HD
—
Heating
Device
IFR
—
Indoor
Fan
Relay
IMS
—
Indoor
Motor
Starter
LLS
—
Liquid
Line
Solenoid
R
—
Relay
(Accessory)
SDR
-
Solenoid
Dropping
Relay
SR
—
Solenoid
Relay
TB
—
Terminal
Board
TC
—
Thermostat,
Cooling
TH
—
Thermostat,
Heating
-
Factory
Wired
-Field
Wired
|
|
Terminal
Board
Conn.
at
Unit
^Field
Supplied
Fig.
11
-
Control
Circuit
Wiring
with
24-Volt
Accessories
(38AB
Units
Only)
7
772