Compressor
Mounting
38AD024,028,034
UNITS
-
As
shipped,
com¬
pressor
is
held
down
by
special
self-locking
bolts
and
plain
lockwashers.
After
unit
is
installed,
remove
the
self-locking
bolts
one
at
a
time
and
reassemble
with
flanged
washers
and
neoprene
snubbers
as
shown
in
Fig.
4.
Special
flanged
wash¬
ers
and
neoprene
snubbers
are
shipped
in
a
cloth
bag
tied
to
one
of
the
compressor
feet.
Tighten
all
four
bolts.
Then,
loosen
each
until
the
flanged
washer
can
be
moved
sidewise.
38AD044,
38AB054,064
AND
084
UNITS
(com¬
pressors
are
mounted
on
a
common
support
channel)
Remove
the
four
shipping
bolts
from
mounting
channels
prior
to
start-up.
Fig.
4
Compressor
Mounting
(38AD024,028
and
034)
Fan
Thermostat
Route
the
thermostat
control
bulb
and
capillary
(located
in
compressor
section)
thru
grommeted
hole
in
compressor
section
base
pan.
Do
not
kink
capillary.
Position
bulb
in
inlet
ah
stream
and
secure
to
inlet
ah
flange
adjacent
to
compressor
section.
Use
clamp
and
screw
provided
in
parts
package.
If
accessory
head
pressure
control
damper
section
is
used,
secure
bulb
to
air
inlet
side
of
damper.
Use
hole
in
damper
frame.
Integrate
Unit
(38AB054.064
and
084
only)
Connect
refrigerant
piping
between
the
two
sec¬
tions,
using
materials
furnished
with
unit.
Arrange
discharge
and
liquid
lines
as
shown
in
Fig.
5
and
braze
as
indicated.
Electrically
connect
unit
control
box
and
junc¬
tion
box
on
coil
(only)
section
by
using
flexible
fan
conduit
furnished
in
the
unit.
Use
the
mating,
quick-connect,
polarized
plugs
furnished
in
the
two
sections
to
make
the
wire
connections.
Motormaster®
(32
Series)
Head
Pressure
Controller
Refer
to
MOTORMASTER
Instructions
shipped
with
this
accessory,
plus
the
following
information.
Control
box
and
sensor
location
is
shown
in
Fig.
6.
Electrical
connections
are
shown
in
Fig.
7.
Refer
to
unit
label
diagram
as
requhed.
On
200-,
208-
and
230-volt
units,
outdoor
fan
motor
no.
1
(OFMj),
located
nearest
the
compressor,
may
be
used
with
MOTORMASTER
without
modification.
For
460-
and
575-volt
units,
refer
to
Table
4
for
field-supplied
components
needed
with
MOTORMASTER.
Fig.
6
-
MOTORMASTER
Control
Box
and
Sensor
Location
3