27
ELECTRIC HEATER DATA, INDOOR UNITS (cont)
LEGEND
*Values shown are for single-point connection of electric heat accessory and air handler.
†Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine heater
capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v capacity (kW) by the
factor shown in the table below for the unit voltage.
2. The following equation converts kW of heat energy to Btuh: kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total external static pressure
of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied motors.
UNIT
40RMQ
HEATER
PART N O.
V-PH-Hz
FAN MOTOR
ELECTRIC HEATERS(S)
MCA* MOCP*
Nominal
Capacity
(kW)
Actual Capacity (kW)
FLA
Hp kW FLA Stage 1 Stage 2 Total
016
CAELHEAT016A00 240-3-60
3.7 2.76 10.2 10 10.0 — 10.0 24.1 42.8 50
5.0 3.73 12.8 10 10.0 — 10.0 24.1 46.1 50
CAELHEAT017A00 480-3-60
3.7 2.76 4.8 10 10.0 — 10.0 12.0 21.0 25
5.0 3.73 6.4 10 10.0 — 10.0 12.0 23.0 25
CAELHEAT018A00 575-3-60
3.0 2.24 3.8 10 10.0 — 10.0 10.0 17.3 20
5.0 3.73 5.1 10 10.0 — 10.0 10.0 19.6 20
CAELHEAT019A00 240-3-60
3.7 2.76 10.2 20 20.0 — 20.0 48.1 73.4 80
5.0 3.73 12.8 20 20.0 — 20.0 48.1 76.1 80
CAELHEAT020A00 480-3-60
3.7 2.76 4.8 20 20.0 — 20.0 24.1 36.1 40
5.0 3.73 6.4 20 20.0 — 20.0 24.1 39.1 40
CAELHEAT021A00 575-3-60
3.0 2.24 3.8 20 20.0 — 20.0 20.1 29.9 30
5.0 3.73 5.1 20 20.0 — 20.0 20.1 31.5 35
CAELHEAT022A00 240-3-60
3.7 2.76 10.2 30 20.0 10.0 30.0 72.2 103.0 110
5.0 3.73 12.8 30 20.0 10.0 30.0 72.2 106.2 110
CAELHEAT023A00 480-3-60
3.7 2.76 4.8 30 20.0 10.0 30.0 36.1 51.1 60
5.0 3.73 6.4 30 20.0 10.0 30.0 36.1 53.1 60
CAELHEAT024A00 575-3-60
3.0 2.24 3.8 30 20.0 10.0 30.0 30.1 42.4 50
5.0 3.73 5.1 30 20.0 10.0 30.0 30.1 44.0 50
CAELHEAT025A00 240-3-60
3.7 2.76 10.2 50 30.0 20.0 50.0 120.3 163.1 175
5.0 3.73 12.8 50 30.0 20.0 50.0 120.3 166.4 175
CAELHEAT026A00 480-3-60
3.7 2.76 4.8 50 30.0 20.0 50.0 60.1 81.2 90
5.0 3.73 6.4 50 30.0 20.0 50.0 60.1 83.2 90
CAELHEAT027A00 575-3-60
3.0 2.24 3.8 50 30.0 20.0 50.0 50.2 67.5 70
5.0 3.73 5.1 50 30.0 20.0 50.0 50.2 69.1 70
FLA —
Full Load Amps
Hp —
Horsepower
MCA —
Minimum Circuit Amps
MOCP —
Maximum Overcurrent Protection (Amps)
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240
0.694 0.751 0.918 1 — — —————
480
————0.694 0.84 0.918 1 ———
575
————————0.915 1 1.089