38BC / 38BH
R-410A
Cooling only and heat pump split system outdoor units
ENGLISH
GB - 1
For operation and maintenance instructions of this unit as well as installation
instructions of the indoor unit, refer to the relevant manuals.
Contents
Page
Dimensions and weight ................................................................................................................. 2
Connections................................................................................................................................... 2
Minimum clearances...................................................................................................................... 3
Operating limits.............................................................................................................................. 3
System charge............................................................................................................................... 3
General information ....................................................................................................................... 4
Warnings: avoid ............................................................................................................................. 5
Refrigerant connections ................................................................................................................ 6/8
Electrical connections ................................................................................................................... 9/10
Electrical data ................................................................................................................................10
Pump down and check the refrigerant charge ............................................................................... 11
Maintenance .................................................................................................................................. 12
Troubleshooting ............................................................................................................................. 12
Guide for the owner and accessories ............................................................................................ 12
Installation instructions supplement .............................................................................................. 13
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH R-410A – QUICK REFERENCE GUIDE
• R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical
position with the valve at the top.
• R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device
in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
• R-410A, as other HFCs, is only compatible with oils selected by the compressor manufacturer.
• A vacuum pump is not enough to remove moisture from oil.
• Oils absorb moisture rapidly. Do not expose oil to atmosphere.
• Never open system to atmosphere while it is under vacuum.
• When the system must be opened for service, break vacuum with dry nitrogen.
• Do not vent R-410A into the atmosphere.
• Use only Carrier matching indoor units (Table I).
Unit size Oil type Quantity cc
07 PVE 440
09 PVE 500
12 PVE 670
14 PVE 670
Table I
Cooling only Heat pump Hi-Wall Hi-Wall Console Cassette Satellite
Power
models models
series
series series series series
supply
(A/C) (H/P)
“42PHQ---N”
“42HMC---N” “42VMC---N” “40KMC---N” “40SMC---N”
38BC-007G 38BH-007G 007 007 — — —
38BC-009G 38BH-009G 009 009 009 — 009
38BC-012G 38BH-012G 012 012 012 012 012
38BC-014G 38BH-014G 014 014 014 — — 230V ~ 50Hz
38BCS009G — 009 009 009 — 009
38BCS012G — 012 012 012 012 012
38BCS014G — 014 014 014 — —