Detailed cooling capacities* continued
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length
and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835
Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of
indoor coil air per degree above 80°F (27°C).
When the required data falls between the published data, interpolation may be performed.
** Unit kw is total of indoor and outdoor unit kilowatts.
EWB Entering Wet Bulb
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh
Tot
Sys
Kw**
Capacity
MBtuh
Tot
Sys
Kw**
Capacity
MBtuh
Tot
Sys
Kw**
Capacity
MBtuh
Tot
Sys
Kw**
Capacity
MBtuh
Tot
Sys
Kw**
Capacity
MBtuh
Tot
Sys
Kw**Total Sens Total Sens Total Sens Total Sens Total Sens Total Sens
38CKC060-37, 57, 67 Outdoor Section With CC5A/CD5AW060 Indoor Section
1775
72 65.64 33.89 5.33 63.80 33.32 5.81 61.47 32.48 6.34 58.69 31.45 6.92 55.71 30.33 7.54 52.51 29.14 8.18
67 60.86 41.99 5.23 58.67 41.16 5.71 56.15 40.11 6.23 53.36 38.91 6.81 50.21 37.62 7.34 46.77 36.22 7.90
62 55.51 49.61 5.13 53.16 48.46 5.57 50.64 47.19 6.02 47.87 45.76 6.51 44.88 44.10 7.03 41.81 41.81 7.58
57
52.57 52.57 5.07 50.70 50.70 5.48 48.79 48.79 5.96 46.71 46.71 6.47 44.36 44.36 7.00 41.83 41.83 7.59
2000
72 66.37 34.83 5.44 64.52 34.34 5.92 62.25 33.67 6.45 59.43 32.67 7.03 56.43 31.61 7.64 53.19 30.45 8.28
67 61.83 43.95 5.34 59.63 43.24 5.81 57.00 42.23 6.33 54.19 41.11 6.90 51.04 39.81 7.49 47.54 38.42 8.05
62 56.59 52.46 5.24 54.18 51.25 5.72 51.59 49.85 6.17 48.67 48.67 6.65 45.97 45.97 7.20 43.35 43.35 7.79
57
54.51 54.51 5.20 52.64 52.64 5.64 50.62 50.62 6.13 48.40 48.40 6.64 45.99 45.99 7.20 43.37 43.37 7.79
2250
72 66.96 35.78 5.56 65.17 35.42 6.04 62.90 34.87 6.57 60.06 33.95 7.15 57.04 32.93 7.75 53.79 31.82 8.39
67 62.64 45.96 5.46 60.40 45.42 5.93 57.74 44.50 6.44 54.88 43.44 7.01 51.76 42.19 7.64 48.17 40.74 8.22
62 57.48 55.24 5.35 55.10 53.95 5.83 52.51 52.51 6.32 50.04 50.04 6.84 47.55 47.55 7.41 44.79 44.79 7.99
57
56.36 56.36 5.34 54.44 54.44 5.82 52.34 52.34 6.32 50.06 50.06 6.84 47.57 47.57 7.41 44.81 44.81 7.99
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
CC5A/CD5AA 060 0.96 0.98 CC5A/CD5AW 060 0.98 0.96
CC5A/CD5AW 060 1.00 1.00 CE3AA 060 0.98 0.97
CE3AA 060 1.00 1.00 CK3BA 060 0.98 0.96
CK3BA 060 0.98 1.00 CK5A/CK5BA 060 0.98 0.96
CK5A/CK5BA 060 0.98 1.00 CK5A/CK5BT 060 0.98 0.96
CK5A/CK5BT 060 0.98 1.00 CK5A/CK5BX 060 1.00 0.96
CK5A/CK5BX 060 1.02 1.01
COILS + 58U(H,X)V120-20 VARIABLE SPEED FURNACE
F(A,B)4AN(F,B,C) 060 1.01 1.04 CC5A/CD5AA 060 0.96 0.97
FB4ANB 070 1.02 1.02 CC5A/CD5AW 060 0.98 0.97
FC4BN(F,B) 060 1.01 1.04 CE3AA 060 0.98 0.98
FC4BNB 070 1.02 1.02 CK3BA 060 0.98 0.97
FG3AAA 060 0.99 1.00 CK5A/CK5BA 060 0.98 0.97
40FKA/FK4CNB 006 1.02 0.97 CK5A/CK5BT 060 0.98 0.97
COILS + 58U(H,X)V100-20 VARIABLE SPEED FURNACE CK5A/CK5BX 060 1.00 0.97
CC5A/CD5AA 060 0.96 0.96 ——