Guide specifications
GENERAL
System Description
Outdoor-mounted, air-cooled, split-system air conditioner 
unit suitable for ground or rooftop installation. Unit consists 
of a hermetic compressor, an air-cooled coil, propeller-type 
condenser fan, and a control box. Unit will discharge supply 
air upward as shown on contract drawings. Unit will be used 
in a refrigeration circuit to match up to a packaged fan coil or 
coil unit.
Quality Assurance
Unit will be rated in accordance with the latest edition of 
ARI Standard 210.
Unit will be certified for capacity, efficiency, and listed in 
the latest ARI directory.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards 
and will carry the UL label of approval. Unit will have c-UL 
approval.
Unit cabinet will be capable of withstanding Federal Test 
Method Standard No. 141 (Method 6061) 500-hr salt spray 
test.
Air-cooled condenser coils will be leak tested at 150 psig 
and pressure tested at 300 psig.
Unit constructed in ISO 9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored 
and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
PRODUCTS
Equipment
Factory-assembled, single-piece, air-cooled air conditioner 
unit. Contained within the unit enclosure is all factory 
wiring, piping, controls, compressor, refrigerant charge 
(R22), and special features required prior to field start-up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel, 
bonderized, and coated with a powder coat paint.
F
ans
Condenser fan will be direct-drive propeller type, 
discharging air upward.
Air-Cooled, Split-System
Air Conditioner
38CKC
1-1/2 to 5 Tons Nominal
Condenser fan motors will be totally enclosed, 1-phase type 
with class B insulation and permanently lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with PVC-coated 
steel wire safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically 
bonded to copper tubes which are then cleaned, dehydrated, 
and sealed.
Refrigeration Components
Refrigeration circuit components will include liquid line 
shutoff valve with sweat connections, suction line shutoff 
valves with sweat connections, system charge of R-22 
refrigerant, and compressor oil.
Operating Characteristics
The capacity of the unit will meet or exceed _____ Btuh at 
a suction temperature of _____ °F. The power consumption 
at full load will not exceed _____ kw.
Combination of the unit and the evaporator or fan coil unit 
will have a total net cooling capacity of _____ Btuh or 
greater at conditions of _____ CFM entering air temperature 
at the evaporator at _____ °F wet bulb and _____ °F dry bulb, 
and air entering the unit at _____ °F.
The system will have an SEER of _____ Btuh/watt or 
greater at DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be _____ v, 
single phase, 60 hertz. The unit will be capable of 
satisfactory operation within voltage limits of _____ v 
to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of this literature identifying accessories 
and descriptions for specific features and available 
enhancements.