5
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
S 3--phase scroll compressors are rotation sensitive.
S A flashing LED on phase monitor indicates reverse
rotation. (See Fig. 4 and Table 2.)
S This will not allow contactor to be energized.
S Disconnect power to unit and interchange 2 field wiring
leads on unit contactor.
!
CAUTION
CHECK CHARGE
Factory charge amount and desired subcooling are shown on unit
rating plate. Charging method is shown on information plate inside
unit. To properly check or adjust charge, conditions must be
favorable for subcooling charging. Favorable conditions exist
when the outdoor temperature is between 70_F and 100_F
(21.11_C and 37.78_C), and the indoor temperature is between
70_F and 80_F (21.11_C and 26.67_C). Follow the procedure
below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge
by adding or removing 0.6 oz/ft of 3/8 liquid line above or below
15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow
system to operate in cooling mode at least 15 minutes. If conditions
are favorable, check system charge by subcooling method. If any
adjustment is necessary, adjust charge slowly and allow system to
operate for 15 minutes to stabilize before declaring a properly
charged system.
If the indoor temperature is above 80_F (26.67_C), and the
outdoor temperature is in the favorable range, adjust system charge
by weight based on line length and allow the indoor temperature to
drop to 80_F (26.67_C) before attempting to check system charge
by subcooling method as described above.
If the indoor temperature is below 70_F (21.11_C), or the outdoor
temperature is not in the favorable range, adjust charge for line set
length above or below 15ft (4.57 m) only. Charge level should then
be appropriate for the system to achieve rated capacity. The charge
level could then be checked at another time when the both indoor
and outdoor temperatures are in a more favorable range.
NOTE: If line length is beyond 80 ft (24.38 m) or greater than 20
ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
Compressor damage may occur if system is overcharged.
!
CAUTION
CARE AND MAINTENANCE
For continuing high performance and to minimize possible
equipment failure, it is essential that periodic maintenance be
performed on this equipment. Consult your servicing contractor or
Owner’s Manual for proper frequency of maintenance. Frequency
of maintenance may vary depending upon geographic areas, such
as coastal applications.
Leave Owner’s Manual with homeowner. Explain system
operation and maintenance procedures outlined in manual.
24 VAC HOT
24 VAC COM
R
C
G
W/W1
Y/Y2
R
C
C
A/C
THERMOSTAT
Typical
FAN COIL
AIR
CONDITIONER
G
W2
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN
24 VAC HOT
24 VAC COM
R
C
G
W/W1
Y/Y2
R
C
C
A/C
THERMOSTAT
Typical
FURNACE
AIR
CONDITIONER
Y
G
W
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN
A02326
Fig. 5 --- Generic Wiring Diagrams
(See Thermostat Installation Instructions for wiring specific unit combinations)