EasyManua.ls Logo

Carrier 38KCR009713 - Heating Mode

Carrier 38KCR009713
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service manual
22
8.7 Heating mode
8.7.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve must
delay 2 minutes compared with compressor if the compressor changed into non-heating mode or turned off.
4-way valve doesn't delay in dehumidifying mode
8.7.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except for
the defrosting mode or the end of defrost
8.7.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes after
starting and then judge temperature. Meanwhile other protections are still valid.
Ts+2*
T
Room temp. up
Room temp. down
Ts+3*
Compressor and
outdoor fan off
Compressor and
outdoor fan on
Ts
* This parameter can be changed from 0 to 3
8.7.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function
prevails.
Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
T
T temp. up
T temp. down
TE2
Setting fan speed
Fan off
Breeze
TE3
TE1
TE4
8.7.5 Auto wind at heating mode (T=indoor temp.)

Table of Contents

Other manuals for Carrier 38KCR009713

Related product manuals