16
ELECTRICAL DATA
Table 9 — Electrical Data
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA - Full Load Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Over-Current Protection
RLA - Rated Load Amps
CONNECTION DIAGRAMS
Fig. 23 — Connection Diagram 12K (115V)
Fig. 24 — Connection Diagram 9K-36K (208-230V)
NOTES:
1. Do not use the thermostat wire for any connection between indoor and outdoor units.
2. All connections between the indoor and outdoor units must be made as shown in Figures 23 - 24. The connections are sensitive to polarity and
will result in a fault code.
Outdoor Unit 12K(115V) 9K(208/230V) 12K(208230V) 18K(208/230V) 24K(208/230V) 30K(208/230V) 36K(208/230V)
Minimum Circuit Ampacity
(MCA)
A19 15 15 16 25 23 28
Maximum Overcurrent
Protection Ampacity (MOPA)
A25 15 15 25 35 30 35
Voltage-Phase-Frequency 115-1-60 208/230-1-60
Max – Min Voltage Range 127-104 253-187
Cooling
Running Current (A) 8 2.5 3.72 6.3 8.1 11.4 18.5
Power Consumption (W) 923 556 857 1440 1845 2605 4235
Power Factor (%) 81.54 95 95.2 95 94 96.5 98.7
Heating
Running Current Range (A) 8.7 4.1 4.1 7.3 10.9 14.7 18.3
Power Consumption (W) 1000 907 907 1700 2500 3380 4200
Power Factor (%) 81.35 96.4 94.9 95 96 97.6 98.7

Other manuals for Carrier 38MARB