CLEARANCES − OUTDOOR
A
D
B
Air-outlet
Air-inlet
C
E
Fig. 5 - Outdoor Unit Clearance
Table 5—Outdoor Unit Clearance Dimensions
UNIT MINIMUM VALUE in. (mm)
A 24 (610)
B 24 (610)
C 24 (610)
D 4 (101)
E 4 (101)
NOTE:  The outdoor unit must be mounted at least 2in. (50mm) above the maximum anticipated snow depth.
118in (300cm) or more
19in (48cm) or more 
on a multiple parallel 
unit arrangement
4in (10cm) or more on 
a single parallel unit 
arrangement
24in (60cm) 
or more
59in (150cm) 
or more on a 
multiple parallel 
unit arrangement
24in (61cm) or more 
on a single parallel 
unit arrangement
9.8in (25cm) 
or more for 
proper airow
24in (61cm) or 
more is 
recommended 
for service
9.8in (25cm)
or more for proper airow 
24in (61cm) 
or more is 
recommended 
for service
Fig. 6 - Clearances for multiple units