FILE NO. SVM-07018
– 67 –
White Black
Red
10-8-5. Outdoor unit
1 Compressor
(Model : DA89X1C-23FZ)
2 Outdoor fan motor
(Model : WLF-240-30A-1)
3 Compressor thermo. Bimetal
type (Model : PW - 2AL)
4 Outdoor temperature sensor
(TO), outdoor heat exchanger
temperature sensor (TE)
No. Part name Checking procedure
Measure the resistance value of each winding by using the tester.
Under 20°C
Measure the resistance value of winding by using the tester.
For details, refer to Section 10-9.
Check conduction by using the tester.
Disconnect the connector, and measure resistance value with the
tester. (Normal temperature)
TGa : Heat pump model only.
TO, TE : Refer to the TA, TC characteristic table in Indoor (Refer to
Table 10-8-3, No.1).
Position Resistance value
Red - White
White - Black 0.51 to 0.57Ω
Black - Red
Under 20°C
1
Red
Black
White
4
25
36
Red
Black White
1 : White 4 : −
2 : − 5 : −
3 : Red 6 : Black
Position Resistance value
Black - Red ~ 237Ω
Black - White ~ 380Ω