6
Electrical data
* Permissible limits of the voltage range at which unit will operate satisfactorily.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed
cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated
(non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used,
consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time-delay fuse.
FLA — Full Load Amps
LRA — Locked Rotor Arms
MCA — Minimum Circuit Amps
RLA — Rated Load Amps
NOTE: Control circuit is 24-v on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/
compressors contain internal overload protection.
SOUND POWER (dBA)
UNIT SIZE-
SERIES V/PH
OPER VOLTS* COMPR
FAN
FLA MCA
60°C
MIN
WIRE
SIZE†
75°C
MIN
WIRE
SIZE†
60°C
MAX
LENGTH
(Ft)‡
75°C
MAX
LENGTH
(Ft)‡
MAX
FUSE**
OR CKT
BKR AMPSMax Min LRA RLA
024-30
208/230/1 253 187
61.0 13.5 0.8 17.6 14 14 44 42 25
030-30 72.5 14.7 0.8 19.2 14 14 41 39 30
036-30 83.0 15.4 1.1 20.2 12 12 62 59 30
042-30 105.0 18.6 1.1 24.4 10 10 80 76 40
048-30 109.0 20.5 1.4 27.0 10 10 73 70 40
060-31 158.0 27.6 1.4 35.9 8 8 85 80 60
UNIT SIZE-SERIES SOUND LEVEL
024-30 70
030-30 71
036-30 71
042-30 74
048-30 76
060-31 78