E6 OR EB: DC FAN ERROR
DEFINITION
Fan rotation is less than 240 RPM for 20 seconds during operation.
Fan rotation difference between the transient RPM and target one is larger than set value for three minutes.
Eb will be reported on DIS1 if E6 occurs two times within ten minutes.
POSSIBLE CAUSES
Burned out motor
Incorrect wiring within electric control box
Damaged power drive board
Damaged main board of ODU
A210281
Fig. 46 —E6 or Eb Troubleshooting Chart
* NOTE 1: If resistance difference between the tested value and the one shown below is larger than 30%, the motor is burned out.
* NOTE 2: Check the power output from main board and connection wires before replacing it.
Between two terminals Red and Black White and Black Yellow and Black Blue and Black
Resistance (KΩ)
1000
1.2 200
1000