Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
Case 4
A210232
Fig. 17 —Piping Design (Case 4)
Bends in piping cause pressure loss during transportation of refrigerant, so fewer bends increases performance.
The equivalent length of each bend is 1.64 feet.
The equivalent length of each Y-Joint or header is 1.64 feet.
Total “downstream indoor capacity” is the total capacity of all the indoor units connected downstream.
The pipe length difference from the first branch to each indoor unit must not exceed 49 feet.
Table 13 —Piping Length
Table 14 —Selection of “L1”
* When the length of “L1” > 230 feet, the gas pipe should be increased from 5/8” to 3/4” or from 3/4” to 7/8”. The pipe adapter must be
located as close as possible to the outdoor unit.
Table 15 —Selection of L3~5, A~F
Item Piping in the Figure Maximum Length Equivalent Length
Total piping length L1 + L3 + L4 + L5 + L6 + A + B + C + D + E + F + G + H 492 -
Maximum distance from ODU to farthest IDU
L1 + L4 + A, L1 + L4 + B, L1 + L4 + C, L1 + L4 + D, L1 +
L3 + L6 + E, L1 + L3 + L6 + F
L1 + L3 + L5 + G, L1 + L3 + L5 + H
296 328
First branch to farthest IDU
L4 + A, L4 + B, L4 + C, L4 + D, L3 + L6 + E, L3 + L6 + F,
L3 + L5 + G, L3 + L5 + H
131 -
Height between ODU and IDU (ODU above IDU) H 164 -
Height between ODU and IDU (ODU below IDU) H 131 -
Height between IDU and IDU h1 49 -
Height between first branch and IDU h2 49 -
Model Gas Pipe Liquid Pipe
38VMB036HDS3-1
5/8 *
3/838VMB048HDS3-1
38VMB060HDS3-1 3/4 *
Downstream Indoor Capacity (KBtu/h) Gas Pipe Liquid Pipe
Capacity ≤ 15K 1/2 1/4
15K < Capacity ≤ 78K 5/8 3/8