EasyManua.ls Logo

Carrier 38VZ - Refrigerant Line Selection

Carrier 38VZ
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
NOTE 1: This control is compatible with any kind of
electromechanical or electronic control (without anticipation
resistors) with the following features:
- Voltage at 24 V AC
50VZ units standard connections:
R Connection to 24 V
L Protection device indication
C Common 24 V
G Ventilation
Y1 First stage cooling
Y2 Second stage cooling
W1 First stage heating (option)
W2 Second stage heating (option)
50PZ units standard connections:
R Connection to 24 V
L Protection device indication
C Common 24 V
G Ventilation
Y1 First stage (cooling/heating)
Y2 Second stage (cooling/heating)
W1 First stage heating (option)
O Reversing valve*
* The O connection is activated in cooling.
NOTE 2: If the thermostat wiring is incorrect, the control will
be blocked (red LED on) and all the outlets will be deactivated
when unit power is supplied.
NOTE 3: The thermostat cables should be separate from any
220 V or 380 V cable.
Refrigerant line connections (38VZ/PZ and 40PZ)
To guarantee correct unit performance ensure that the line
length and number of bends are kept to a minimum. Avoid pipe
kinking by using large radius bends.
IMPORTANT: Always use refrigerant-grade deoxidized and
dehydrated copper tubing between the indoor and outdoor
units.
Before connecting the refrigerant lines carefully follow the
steps below:
- Remove the nitrogen holding charge from the refrigerant
circuits.
- Select the diameter of the copper tubing according the the
units installed and according to the distance between the
indoor and outdoor units.
- Use silver alloy rod for soldering purposes, and ensure
that this work is done in a nitrogen atmosphere.
- To avoid oxidation insulate the refrigerant lines
adequately.
- Pull a vacuum in the refrigerant circuit until a pressure of
6.9 Pa is maintained for at least 2 hours.
- Charge the refrigerant circuit with the necessary amount
of R-407C refrigerant (in accordance with table 1 and the
length of the refrigerant lines).
- Check there are no refrigerant leaks.
Refrigerant line selection
General
When designing refrigerant lines the following must be kept in
mind:
- Depending on the unit arrangement:
Fig. 22 - Refrigerant lines option A
Heat pump (discharge line)
Outdoor unit
Indoor unit
Heat pump
Liquid line
Cooling
Gas line
Cooling (suction line)
Suction/discharge line:
- A siphon at the base of the vertical pipe run and inter-
mediate siphons every 8 m or oil separators are needed.
- Most unfavourable condition: the suction speed in the
vertical pipe run must be more than 6 m/s.
Fig. 23 - Refrigerant lines option B
Heat pump (discharge line)
Outdoor unit
Indoor unit
Heat pump
Liquid line
Cooling
Gas line
Cooling (suction line)
Suction/discharge line:
- For heat pumps a siphon is required in the base of the
vertical pipe run.
- The intermediate siphon can be omitted.
- For cooling only units siphons are not required.
- Most unfavourable condition: the suction/discharge
speed in the vertical pipe run must be more than 6 m/s.

Other manuals for Carrier 38VZ

Related product manuals