14
Heat pump heating performance
See notes on pg. 17.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES
∞
F
–3 7 17 27 37 47 57 67
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
EDB CFM Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡
38YCA018-33, 34 Outdoor Section With F(A,B)4ANF018 Indoor Section
65
600
650
700
7.22
7.31
7.40
6.65
6.73
6.81
1.27
1.29
1.31
8.97
9.07
9.16
8.24
8.33
8.42
1.35
1.37
1.38
10.9
11.0
11.1
9.92
10.0
10.1
1.43
1.44
1.45
12.9
13.1
13.2
11.5
11.6
11.7
1.50
1.51
1.53
15.2
15.4
15.5
13.9
14.0
14.1
1.59
1.60
1.61
17.7
17.9
18.0
17.7
17.9
18.0
1.69
1.70
1.71
20.8
21.0
21.1
20.8
21.0
21.1
1.83
1.83
1.84
23.8
24.0
24.2
23.8
24.0
24.2
1.98
1.99
2.00
70
600
650
700
6.96
7.05
7.13
6.40
6.48
6.56
1.29
1.31
1.32
8.69
8.79
8.88
7.99
8.08
8.16
1.37
1.39
1.40
10.6
10.7
10.8
9.65
9.76
9.85
1.45
1.46
1.48
12.6
12.7
12.9
11.2
11.3
11.4
1.53
1.54
1.56
14.9
15.0
15.2
13.5
13.7
13.8
1.62
1.63
1.64
17.3
17.5
17.6
17.3
17.5
17.6
1.72
1.73
1.74
20.3
20.5
20.7
20.3
20.5
20.7
1.86
1.87
1.88
23.4
23.6
23.7
23.4
23.6
23.7
2.02
2.02
2.03
75
600
650
700
6.67
6.76
6.85
6.14
6.22
6.30
1.30
1.32
1.34
8.41
8.51
8.61
7.73
7.82
7.91
1.39
1.41
1.42
10.3
10.4
10.5
9.38
9.48
9.58
1.48
1.49
1.50
12.3
12.4
12.5
10.9
11.0
11.1
1.56
1.57
1.59
14.5
14.7
14.8
13.2
13.4
13.5
1.66
1.67
1.68
16.9
17.1
17.3
16.9
17.1
17.3
1.76
1.77
1.78
19.9
20.1
20.2
19.9
20.1
20.2
1.90
1.91
1.91
22.9
23.1
23.3
22.9
23.1
23.3
2.05
2.06
2.07
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating
Indoor
Section Size
Heating
Capacity Power Capacity Power
CC5A/CD5A/
CD5BA
018 0.97 0.99 FA1ANA 018 1.00 0.99
024 1.00 0.97 024 1.02 0.97
CD3(A,B)A 018 0.97 0.99 FC4ANF 018 1.02 0.98
024 1.00 0.97 FD3ANA 024 1.00 0.96
CE3AA 024 1.00 0.97 FF1ANA 018 1.00 0.99
CF5AA 024 1.00 0.97 024 1.01 0.95
FB(4,5)AN(A,F) 018 1.00 1.00 FG3AAA 024 0.96 0.94
024 1.03 0.99 F(A,B)4ANF 018 1.00 1.00
— — — 024 1.03 0.99
38YCA/YCN024-35, 36 Outdoor Section With F(A,B)4ANF024 Indoor Section
65
700
800
900
9.37
9.59
9.79
8.62
8.82
9.00
1.56
1.59
1.63
11.7
11.9
12.2
10.8
11.0
11.2
1.66
1.69
1.72
14.2
14.5
14.7
12.9
13.2
13.4
1.75
1.77
1.80
16.8
17.1
17.4
14.9
15.2
15.4
1.84
1.86
1.88
19.6
19.9
20.2
17.8
18.1
18.4
1.92
1.94
1.96
22.7
23.2
23.5
22.7
23.2
23.5
2.02
2.04
2.05
26.6
27.1
27.4
26.6
27.1
27.4
2.17
2.17
2.16
30.2
30.3
30.2
30.2
30.3
30.2
2.28
2.25
2.23
70
700
800
900
8.87
9.11
9.31
8.16
8.38
8.56
1.57
1.60
1.64
11.3
11.5
11.7
10.4
10.6
10.8
1.67
1.70
1.73
13.7
14.0
14.2
12.5
12.8
13.0
1.77
1.80
1.83
16.3
16.6
16.9
14.5
14.8
15.0
1.86
1.89
1.91
19.1
19.5
19.7
17.4
17.7
18.0
1.96
1.98
1.99
22.2
22.6
22.9
22.2
22.6
22.9
2.06
2.07
2.09
26.0
26.5
26.9
26.0
26.5
26.9
2.20
2.21
2.21
29.8
29.9
30.0
29.8
29.9
30.0
2.34
2.30
2.30
75
700
800
900
8.34
8.58
8.78
7.67
7.89
8.07
1.57
1.61
1.64
10.8
11.1
11.3
9.95
10.2
10.4
1.68
1.71
1.75
13.3
13.5
13.8
12.1
12.3
12.6
1.79
1.82
1.85
15.8
16.1
16.4
14.1
14.3
14.6
1.89
1.91
1.94
18.6
19.0
19.3
16.9
17.3
17.5
1.99
2.01
2.03
21.6
22.0
22.4
21.6
22.0
22.4
2.10
2.11
2.12
25.3
25.8
26.2
25.3
25.8
26.2
2.24
2.25
2.26
29.0
29.4
29.7
29.0
29.4
29.7
2.38
2.36
2.36
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating
Indoor
Section Size
Heating
Capacity Power Capacity Power
F(A,B)4ANF
024 1.00 1.00
CD3(A,B)A
024 1.00 1.03
030 1.00 0.99 030 1.00 1.03
FD3ANA
024 1.00 1.01
CC5A/CD5A/CD5BW
030 1.00 1.03
030 1.00 0.99
CE3AA
024 1.00 1.02
FF1(A,B)NA
024 1.00 1.01 030 1.00 0.99
030 1.00 0.99
CF5AA
024 1.00 1.02
CC5A/CD5A/CD5BA
024 1.00 1.03 — — —
030 1.00 1.03