28
Detailed cooling capacities* continued
Multipliers for Determining the Performance With Other Indoor Sections
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-89. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C).
** System kw is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
EWB—Entering Wet Bulb
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
38YRA060-30 Outdoor Section With FK4CNB006 Indoor Section
1575
72 66.2 32.7 4.89 63.3 31.7 5.42 60.2 30.5 6.0 57.0 29.4 6.63
67 61.0 41.4 4.82 58.4 40.3 5.35 55.5 39.2 5.9 52.5 38.0 6.54
63†† 57.2 40.5 4.77 54.6 39.4 5.29 52.0 38.2 5.8 49.2 37.0 6.47
62 56.2 49.9 4.76 53.7 48.7 5.28 51.1 47.5 5.8 48.4 46.2 6.46
57 54.0 54.0 4.73 52.1 52.1 5.26 50.1 50.1 5.8 47.8 47.8 6.45
1750
72 67.0 33.9 4.95 64.1 32.9 5.49 60.8 31.7 6.0 57.5 30.5 6.69
67 61.8 43.4 4.89 59.0 42.3 5.41 56.1 41.2 5.9 53.0 39.9 6.61
63†† 57.9 42.4 4.84 55.3 41.2 5.36 52.6 40.0 5.9 49.7 38.8 6.54
62 57.1 52.7 4.83 54.5 51.5 5.35 51.9 50.1 5.9 49.2 48.7 6.53
57 55.7 55.7 4.81 53.6 53.6 5.34 51.4 51.4 5.9 49.0 49.0 6.53
2012
72 67.8 35.6 5.05 64.7 34.5 5.58 61.5 33.3 6.1 58.0 32.2 6.79
67 63.1 46.5 4.99 60.2 45.4 5.52 56.8 44.0 6.0 53.6 42.8 6.70
63†† 58.8 45.1 4.93 56.1 43.9 5.45 53.3 42.7 6.0 50.2 41.5 6.64
62 58.5 56.7 4.93 55.6 55.1 5.45 53.1 53.1 6.0 50.6 50.6 6.65
57 57.7 57.7 4.92 55.5 55.5 5.45 53.2 53.2 6.0 50.7 50.7 6.65
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
F(A,B)4AN(F,B,C) 060 0.97 1.06 CD3(A,B)A 060 0.93 1.04
FB4ANB 070 0.99 1.04
COILS + 58U(H,X)V100-20 VARIABLE-SPEED FURNACE
FC4BN(F,B) 060 0.97 1.06 CC5A/CD5A/CD5BA 060 0.94 1.01
FC4BNB 070 0.99 1.04 CC5A/CD5A/CD5BW 060 0.97 1.00
FG3AAA 060 0.96 1.02 CD3(A,B)A 060 0.94 1.01
FK4BNB 006 1.00 1.01 CE3AA 060 0.97 1.01
FK4CNB 006 1.00 1.00 CJ5A/CK5A/CK5BA 060 0.97 1.00
CC5A/CD5A/CD5BA 060 0.94 1.02 CJ5A/CK5A/CK5BX 060 0.99 0.99
CC5A/CD5A/CD5BW 060 0.96 1.02 CK3BA 060 0.97 1.00
CD3(A,B)A 060 0.94 1.02
COILS + 58U(H,X)V120-20 VARIABLE-SPEED FURNACE
CE3AA 060 0.97 1.03 CC5A/CD5A/CD5BA 060 0.93 1.02
CJ5A/CK5A/CK5BA 060 0.97 1.02 CC5A/CD5A/CD5BW 060 0.96 1.01
CJ5A/CK5A/CK5BN 060 0.97 1.02 CD3(A,B)A 060 0.93 1.02
CJ5A/CK5A/CK5BX 060 0.98 1.02 CE3AA 060 0.97 1.02
CK3BA 060 0.97 1.02 CJ5A/CK5A/CK5BA 060 0.97 1.01
COILS + 58MVP100-20 VARIABLE-SPEED FURNACE CJ5A/CK5A/CK5BX 060 0.98 1.00
CC5A/CD5A/CD5BA 060 0.93 1.04 CK3BA 060 0.97 1.01
CC5A/CD5A/CD5BW 060 0.96 1.04 — — —