Combination ratings* continued
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit.
High-Temp Heating Standard: 70°F (21°C) db indoor entering air temperature and 47°F (8°C) db 43°F (6°C) wb air entering outdoor unit.
Low-Temp Heating Standard: 70°F (21°C) db indoor entering air temperature and 17°F (-9°C) db 15°F (–10°C) wb air entering outdoor unit.
† Outdoor section/indoor section combination tested in accordance with DOE test procedures for heat pumps. Ratings for other combinations are determined
under DOE computer simulation procedures.
‡ Requires hard shutoff TXV; based on computer simulation.
** TDR is on all furnaces, except 58GFA.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA)
INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment
Standard
Rating
Field-Supplied
Accessory‡
TXV
TXV&TDR**
TC COP TC COP
060-30
75
FK4CNB006† 59,000 TDR & TXV 12.50 — — 61,000 3.32 39,000 2.58 8.30/8.50
F(A,B)4AN(F,B)060 57,500 TDR — 11.50 — 61,000 3.06 39,500 2.40 7.80/8.20
FB4ANB070 58,500 TDR — 12.00 — 61,000 3.22 39,500 2.48 8.00/8.20
FC4BN(F,B)060 57,500 TDR & TXV 11.50 — — 61,000 3.06 39,500 2.40 7.80/8.00
FC4BNB070 58,500 TDR & TXV 12.00 — — 61,000 3.22 39,500 2.48 8.00/8.20
FG3AAA060 56,500 None — — 11.50 61,000 2.94 39,000 2.36 7.50/7.70
FK4BNB006 59,000 TDR & TXV 12.50 — — 61,000 3.30 39,000 2.54 8.30/8.50
CC5A/CD5A/CD5BA060 55,500 None — — 11.50 61,000 2.82 38,500 2.30 7.30/7.50
CC5A/CD5A/CD5BW060 56,500 None — — 11.50 61,000 3.00 39,000 2.40 7.70/7.90
CD3(A,B)A060 55,500 None — — 11.50 61,000 2.82 38,500 2.30 7.30/7.50
CE3AA060 57,500 None — — 12.00 61,000 3.00 39,000 2.40 7.70/7.90
CJ5A/CK5A/CK5BA060 57,500 None — — 11.50 61,000 2.94 39,000 2.38 7.50
CJ5A/CK5A/CK5BN060 57,500 None — — 11.50 61,000 2.94 39,000 2.38 7.50
CJ5A/CK5A/CK5BX060 58,000 None — — 12.00 61,000 3.08 39,000 2.44 7.80
CK3BA060 57,500 None — — 11.50 61,000 2.94 39,000 2.38 7.50
COILS + 58MVP100-20 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 55,000 TDR — 11.20 — 61,000 2.80 39,500 2.30 7.20/7.40
CD3(A,B)A060 55,000 TDR — 11.20 — 61,000 2.80 39,500 2.30 7.20/7.40
CC5A/CD5A/CD5BW060 56,500 TDR — 11.50 — 61,000 3.00 39,500 2.40 7.50/7.70
COILS + 58U(H,X)V100-20 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 55,500 TDR — 11.50 — 61,000 2.84 38,500 2.32 7.20/7.40
CD3(A,B)A060 55,500 TDR — 11.50 — 61,000 2.84 38,500 2.32 7.20/7.40
CC5A/CD5A/CD5BW060 57,000 TDR — 12.00 — 61,000 3.04 39,000 2.44 7.80/8.00
CE3AA060 57,500 TDR — 12.00 — 61,000 3.02 39,000 2.42 7.80/8.00
CJ5A/CK5A/CK5BA060 57,500 TDR — 12.00 — 61,000 2.94 38,500 2.40 7.50
CJ5A/CK5A/CK5BX060 58,500 TDR — 12.20 — 61,000 3.12 38,500 2.48 7.80
CK3BA060 57,500 TDR — 12.00 — 61,000 2.94 38,500 2.40 7.50
COILS + 58U(H,X)V120-20 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 55,000 TDR — 11.50 — 61,000 2.80 39,000 2.30 7.20/7.40
CD3(A,B)A060 55,000 TDR — 11.50 — 61,000 2.80 39,000 2.30 7.20/7.40
CC5A/CD5A/CD5BW060 56,500 TDR — 12.00 — 61,000 3.02 39,000 2.42 7.50/7.70
CE3AA060 57,500 TDR — 12.00 — 61,000 3.00 39,000 2.42 7.50/7.70
CJ5A/CK5A/CK5BA060 57,500 TDR — 11.80 — 61,000 2.96 38,500 2.38 7.50
CJ5A/CK5A/CK5BX060 58,000 TDR — 12.00 — 61,000 3.10 38,500 2.46 7.80
CK3BA060 57,500 TDR — 11.80 — 61,000 2.96 38,500 2.38 7.50
SEER — Seasonal Energy Efficiency Ratio LSV — Liquid Solenoid Valve
COP — Coefficient of Performance TDR — Time-Delay Relay
HSPF — Heating Seasonal Performance Factor TXV — Thermostatic Expansion Valve
TC — Total Capacity (Btuh)