3
Physical data
* Tube sizes are for runs up to 50 ft. For tube set over 50 ft, consult Long-Line Application Guideline.
† Charge quantity is for 15 ft of interconnecting tubing. For tubing lengths other than 15 ft, see Long-Line Application Guideline for additional refrigerant
requirements.
NOTE:
See unit Installation Instructions for proper installation.
METERING DEVICE
UNIT SIZE-SERIES 018-31 024-31 030-31 036-31 042-31 048-30 060-30
OPERATING WT (Lb)
198 205 233 223 243 277 352
COMPRESSOR TYPE
Scroll
REFRIGERANT
22
Control
TXV (Cooling)
Charge (Lb)†
5.63 8.88 7.13 10.88 11.88 14.88
COND FAN
Propeller Type, Direct Drive
Air Discharge
Vertical
Air Qty (CFM)
2500 2400 2900 3600
Mtr Rpm (60 hz)
820
COND COIL
Face Area (Sq Ft)
15.15 18.18 24.89
CONNECT (In. ID)
Sweat
Vapor
5/8 3/4 7/8
Liquid
3/8
REFRIG TUBES*
(In. OD)
Vapor
5/8 3/4 7/8 1-1/8
Liquid
3/8
UNIT
SIZE SERIES OUTDOOR PISTON
INDOOR
TXV*
018
31 42 KHATX0901HSO
024
31 49 KHATX1001HSO
030
31 52 KHATX1101HSO
036
31 59 KHATX1201HSO
042
31 63 KHATX1201HSO
048
30 70 KHATX1301HSO
060
30 73 KHATX1401HSO
* TXV must be ordered separately when indoor coil is not equipped with a TXV. TXV listed is for
any approved coil combination. All TXVs are bi-flow, hard shutoff.
M
A
N
U
F
A
C
T
U
R
E
R
C
E
R
T
I
F
I
E
D
T
O
A
R
I
A
S
C
O
M
P
L
Y
I
N
G
W
I
T
H
A
R
I
S
T
A
N
D
A
R
D
2
4
0
U
N
I
T
A
R
Y
H
E
A
T
P
U
M
P
E
Q
U
I
P
M
E
N
T
®
CERTIFICATION APPLIES ONLY WHEN THE
COMPLETE SYSTEM IS LISTED WITH ARI.
CERTIFICATION OF
MANUFACTURING SITE.
As an ENERGY STAR
SM
Partner, Carrier Corporation has deter-
mined that this product meets the ENERGY STAR guidelines for
energy efficiency.