37
Heat pump heating performance continued
Multipliers for Determining the Performance With Other Indoor Sections
* The Btuh heating capacity values shown are net “integrated’’ values from which the defrost effect has been subtracted. The Btuh heating from supplement
heaters should be added to those values to obtain total system capacity.
The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to
obtain total system kilowatts.
EDBEntering Dry Bulb
System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C).
4. Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C).
5. Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C).
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft/indoor coil below = 150 ft (see items 8 and 9 following).
8. For interconnecting refrigerant tube lengths greater than 50 ft, consult Long-Line Application Guideline available from equipment distributor.
9. Not more than 36 in. of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical rise to the valve
connections at the unit.
10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
3 7 1727374757
EDB CFM
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
38YRA060-30 Outdoor Section With FK4CNB006 Indoor Section
65
1575 28.0 25.8 3.81 33.2 30.6 4.02 39.1 35.6 4.24 45.3 40.3 4.4 52.8 48.0 4.81 61.2 61.2 5.20 71.0 71.0 5.73
1750 28.3 26.0 3.82 33.5 30.8 4.01 39.4 35.9 4.22 45.7 40.5 4.4 53.2 48.4 4.76 61.7 61.7 5.14 71.7 71.7 5.65
2012 28.6 26.3 3.84 33.9 31.1 4.02 39.7 36.2 4.21 46.1 40.9 4.4 53.7 48.9 4.72 62.3 62.3 5.09 72.0 72.0 5.52
70
1575 27.7 25.5 3.98 32.9 30.3 4.21 38.7 35.3 4.45 44.9 39.8 4.7 52.1 47.5 5.05 60.5 60.5 5.45 70.2 70.2 5.99
1750 28.0 25.7 3.99 33.2 30.5 4.20 39.0 35.6 4.43 45.2 40.1 4.6 52.6 47.8 4.99 61.0 61.0 5.38 71.6 71.6 5.91
2012 28.3 26.0 4.02 33.5 30.8 4.21 39.4 35.9 4.42 45.6 40.5 4.6 53.1 48.3 4.95 61.6 61.6 5.32 71.5 71.5 5.84
75
1575 27.4 25.2 4.16 32.6 30.0 4.41 38.3 35.0 4.67 44.4 39.4 4.9 51.6 47.0 5.29 59.8 59.8 5.72 69.3 69.3 6.27
1750 27.6 25.4 4.16 32.9 30.2 4.40 38.6 35.2 4.64 44.7 39.7 4.9 52.0 47.3 5.23 60.3 60.3 5.64 70.0 70.0 6.17
2012 28.0 25.7 4.19 33.2 30.5 4.41 39.0 35.6 4.63 45.2 40.1 4.8 52.5 47.8 5.18 60.9 60.9 5.57 70.7 70.7 6.10
Indoor
Section Size
Heating
Indoor
Section Size
Heating
Capacity Power Capacity Power
F(A,B)4AN(F,B,C) 060 1.00 1.09 CD3(A,B)A 060 1.00 1.19
FB4ANB 070 1.00 1.03
COILS + 58U(H,X)V100-20 VARIABLE-SPEED FURNACE
FC4BN(F,B) 060 1.00 1.09 CC5A/CD5A/CD5BA 060 1.00 1.17
FC4BNB 070 1.00 1.03 CC5A/CD5A/CD5BW 060 1.00 1.10
FG3AAA 060 1.00 1.13 CD3(A,B)A 060 1.00 1.17
FK4BNB 006 1.00 1.01 CE3AA 060 1.00 1.10
FK4CNB 006 1.00 1.00 CJ5A/CK5A/CK5BA 060 1.00 1.12
CC5A/CD5A/CD5BA 060 1.00 1.18 CJ5A/CK5A/CK5BX 060 1.00 1.06
CC5A/CD5A/CD5BW 060 1.00 1.11 CK3BA 060 1.00 1.12
CD3(A,B)A 060 1.00 1.18
COILS + 58U(H,X)V120-20 VARIABLE-SPEED FURNACE
CE3AA 060 1.00 1.11 CC5A/CD5A/CD5BA 060 1.00 1.19
CJ5A/CK5A/CK5BA 060 1.00 1.12 CC5A/CD5A/CD5BW 060 1.00 1.10
CJ5A/CK5A/CK5BN 060 1.00 1.12 CD3(A,B)A 060 1.00 1.19
CJ5A/CK5A/CK5BX 060 1.00 1.07 CE3AA 060 1.00 1.11
CK3BA 060 1.00 1.12 CJ5A/CK5A/CK5BA 060 1.00 1.11
COILS + 58MVP100-20 VARIABLE-SPEED FURNACE CJ5A/CK5A/CK5BX 060 1.00 1.06
CC5A/CD5A/CD5BA 060 1.00 1.19 CK3BA 060 1.00 1.11
CC5A/CD5A/CD5BW 060 1.00 1.11