38GL...G / 38GLS...G / 38YY...G / 38YYS...G
Cooling only and heat pump split system outdoor units
GB - 1
ENGLISH
Cooling only
(A/C)
Heat pump (H/P) Hi-Wall series Hi-Wall series
Console series Cassette series
Satellite Power
Cooling only Heat pump “42PHQ---N” “42HMC---N” “42VMC---N” “40KMC---N” “40SMC---N” supply
38GL(S)018G 38YY(S)018G 42PHQ018N 42HMC018N
42VMC018(A)*N
40KMC018N 40SMC018N
38GL(S)024G 38YY(S)024G 42PHQ024N 42HMC024N
42VMC024(A)*N
40KMC024N 40SMC024N
38GL028G 38YY-028G — — 42VMC028 N 40KMC028N 40SMC028N
230V ~ 50Hz
38GL036G 38YY-036G — — 42VMC036 N 40KMC036N 40SMC036N
38GL048G 38YY-048G — — 42VMC048 N 40KMC048N 40SMC048N
*(A)= Aluminium version
Unit size Oil type
Quantity Drier already installed on
cc liquid line of the unit
018 - 024 POE 1120 YES
028 - 036 POE 1250 YES
048 POE 1400 YES
Table I
For operation and maintenance instructions of this unit as well as installation
instructions of the indoor unit, refer to the relevant manuals.
Contents
Page
Dimensions and weight ................................................................................................................. 2
Connections................................................................................................................................... 2
Minimum clearances...................................................................................................................... 3
Operating limits.............................................................................................................................. 3
Accessories ................................................................................................................................... 3
General information ....................................................................................................................... 4
Warnings: avoid ............................................................................................................................. 5
Refrigerant connections ................................................................................................................ 6/8
Electrical connections ................................................................................................................... 9/10
Electrical data ................................................................................................................................10
Pump down and refrigerant circuit................................................................................................. 11
Unit maintenance........................................................................................................................... 12
Troubleshooting and guide for the owner....................................................................................... 12
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH R-410A–QUICK REFERENCE GUIDE
• R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a
vertical position with the valve at the top.
• R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device
in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
• R-410A, as other HFCs, is only compatible with oils selected by the compressor manufacturer.
• A vacuum pump is not enough to remove moisture from oil.
• Oils absorb moisture rapidly. Do not expose oil to atmosphere.
• Never open system to atmosphere while it is under vacuum.
• When the system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
• Do not vent R-410A into the atmosphere.
• Use only Carrier matching indoor units (Table I).