3-2
62-10630
Table 3 -1 Alarm Indications -- Continued
ALARM
Description CORRECTIVE ACTION
Reference
Paragraph
A09 Hot Gas Valve (HGS1)
Current draw of coil high or low (approx 1.6 amp) -- --
high amp draw
Replace coil 4.14.1
A10 Quench Valve (BPV)
Current draw of coil high or low (approx 1.2 amp) -- --
high amp draw
Replace coil 4.14.1
A11 Condenser Pressure Control
Current draw of coil high or low (approx 1.6 amp) -- --
alve (HGS2) high amp draw
Replace coil 4.14.1
A12 Out–of–Range -- High Temper-
Unit out of range for 15 minutes Verify Setting
ature
Verify cooling operation of unit -- --
Hot gas solenoid open 4.14
A13 Out–of–Range Low Tempera-
Unit out of range for more than 15 minutes Verify Setting
ture
Verify heating operation of unit -- --
Heating option not active (Set Configuration) 2.9
A14 Defrost Cycle >45 minutes Unit terminated defrost after 45 minutes -- --
Verify HGS1/HGS2 valve operation 4.14
A15 Setpoint out of range Operator entered invalid setpoint (outside of range) 2.6
Verify configuration settings 2.9
A16 Evaporator drain line heater
(DWR) malfunction
Replace heater -- --
A17 Transformer/Rectifier Thermal
Line voltage low Correct
Overload (RBT) Open
Transformer winding open Replace
High load on rectification system Correct
A18 Electrical Heating Relay
Relay shorted Replace
(Future)
Wiring shorted Correct
A19 Multi--Temp Liquid Solenoid
Valve coil shorted Replace
a
ve
g
amps
raw
[Future]
Wiring shorted Correct
A20 Low Pressure Switch (LPS)
Unit undercharged 4.10.1
Open (Standby)
Liquid line filter--drier restricted 4.5
TXV strainer plugged with foreign material/ice. 4.6
TXV malfunction 4.16
Verify operation of evaporator fans -- --
Failed switch Replace
A21 Compressor Contactor (MC)
Contactor coil open circuit Replace
Open Circuit
Wiring to coil open Check
A22 Condenser Fan Motor (CFM)
Condenser fan motor defective 4.13
Open Circuit
Wiring to motor open Check
A23 Hot Water Solenoid Valve
Valve coil shorted Replace
(H
) Open Circuit
Wiring to coil open Check
A24 Hot Gas Valve (HGS1) Open
Valve coil shorted 4.14.1
Circuit
Wiring to coil open Correct
A25 Quench Valve (BPV) Open
Valve coil shorted Replace
Circuit
Wiring to coil open Correct
A26 Condenser Pressure Control
Valve coil shorted 4.14.1
alve (HGS2) Open Circuit
Wiring to coil open Correct
A27 Evaporator Drain Line Heater
Evaporator drain heater shorted Replace
(D
R) Open Circuit
Verify wiring to heater Correct
A28 Heating Relay (EHR) Open
Relay open circuit Replace
Circuit (Future)
Wiring to coil open Correct