AIR THROW DATA
UNIT
CAPACITY
APPROXIMATE AIR THROW ft. (m)
Low Medium High
009 18 (5.5) 20 (6.1) 23 (7.0)
012 19 (5.8) 21 (6.4) 25 (7.6)
SOUND RATINGS
Outdoor Units
Model Number Sound Power dBA Sound Pressure dBA
3 8 G X Q 0 0 9 --- --- --- 1 65 / 66 54 / 55
3 8 G X Q 0 1 2 --- --- --- 1 65 / 66 54 / 55
Indoor Units
Model Number
High Medium Low
Sound Power
dBA
(Cool / Heat)
Sound Pressure
dBA
(Cool / Heat)
Sound Power
dBA
(Cool / Heat)
Sound Pressure
dBA
(Cool / Heat)
Sound Power
dBA
(Cool / Heat)
Sound Pressure
dBA
(Cool / Heat)
4 0 G X Q 0 0 9 --- --- --- 1 55 / 54 44 / 43 52 / 52 41 / 41 40 / 42 29 / 31
4 0 G X Q 0 1 2 --- --- --- 1 55 / 54 44 / 43 51 / 51 40 / 40 48 / 50 37 / 39
NOTES:
1. Sound power ratings ar e per ARI 270 and ARI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
ELECTRICAL DATA
UNIT
SIZE
SYSTEM
VOLTAGE
OPERATING
VOLTAGE*
COMPRESSOR OUTDOOR FAN INDOOR FAN{
MCA
MAX
FUSE/CB
AMP
V O L T S --- P H --- H Z MAX/MIN RLA LRA FLA HP W VOLTS FLA HP W
009
1 1 5 --- 1 --- 6 0 127/104
4.0 33
.6 .04 30 115
.3 .027 30 20 25
012 4.0 33 .45 .027 20 20 25
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ Indoor fan powered from outdoor unit.
LEGEND
FLA --- F u l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA --- RatedLoadAmps
38/40GXQ