GB - 17
40KMC---N
ENGLISH
System configuration
Table VII
Item Shown on display Options Description
“A”: remote unit A Remote address indoor unit A.
See paragraph "address selector
"
1 “rAdr”“b”:
remote unit
B
Remote address indoor unit
B. See paragraph "address selector
"
“Ab”:
remote units
A and B Default address is both indoor units.
2 “UCFG”
“HP”: heat pump
Refer to the specific instruction sheet
“AC”: cooling only
3 “UAdr”
1-
2
40 with increase of 1 Unit CCN address (Carrier Confort Network)
Default = 1.
4 “ZONE”
1-
2
40 with increase of 1 Number of zone.
Default = 0.
5 “GFdn” 1-
2
40 with increase of 1
Default = 1. (Monosplit systems)
2
39 = configured as T-kit
2
40 = configured as multisplit
6 “A St”
“OF”: The unit remains OFF Choose of operating mode after a power supply
“On”: Unit automatic restarting interruption. Pre-arranged "ON".
System configuration
The unit settings are made at the factory (refer to the specific
instruction sheet).
In the case of system installation other than the original one (as
referred to in the specific instruction sheet) the factory configuration
must be changed.
Such operation must be performed by the installer as follows:
Cooling only configuration (of the system)
• Check all electrical connections (instructions and wiring diagram).
• Insert the batteries into the remote control and leave it OFF.
• Energise the system, turning the power supply ON.
• Press the
and buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
• The display will be cleared, the time segments will display the
first configuration item (rAdr = remote address) and the tempera-
ture segments will display the default value of this configuration
item (Ab = control of both indoor units).
• Press button
repeatedly until “UCFG” is displayed.
• Press either the
or button to change the default value (HP)
to the new value (CO).
• Press the
button to send the configuration to the unit, which
will confirm with a “beep”.
• Press
button to leave the configuration menu.
For other available configuration options, see table VII.
Heat pump configuration (of the system)
• Check all electrical connections (instructions and wiring diagram).
• Insert the batteries into the remote control and leave it OFF.
• Energise the system, turning the power supply ON.
• Press the
and buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
• The display will be cleared, the time segments will display the
first configuration item (rAdr = remote address) and the tempera-
ture segments will display the default value of this configuration
item (Ab = control of both indoor units).
• Press button
repeatedly until “UCFG” is displayed.
• Press either the
or button to change the default value (CO)
to the new value (HP).
• Press the
button to send the configuration to the unit, which
will confirm with a “beep”.
• Press
button to leave the configuration menu.
For other available configuration options, see table VII.
Multisplit/T-Kit configuration
• Check all electrical connections (instructions and wiring diagram).
• Insert the batteries into the remote control and leave it OFF.
• Energise the system, turning the power supply ON.
• Press the
and buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
• The display will be cleared, the time segments will display the
first configuration item (rAdr = remote address) and the tempera-
ture segments will display the default value of this configuration
item (Ab = control of both indoor units).
• Push
button until will appear “GFdn” on the display.
• Through the buttons
and to change the default value “1” into
239 for T-KIT configuration or 240 for MULTISPLIT configuration.
• Press the
button to send the configuration to the unit, which
will confirm with a “beep”.
• Press the
button to exit from this configuration menu.
Note:
When 30 seconds have elapsed and no buttons have been
pressed, the remote controller will automatically exit the
configuration menu and the procedure has to be restarted.
Cooling only configuration (of the remote controller)
• Insert the batteries into the remote controller and leave it OFF.
• Press the
and buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
• The display will be cleared, the temperature segments will display
the first configuration item (CH = remote address) and the time
segments will display the default value of this configuration item
(Ab = control of both indoor units).
• Press button
repeatedly until “rc” is displayed.
• Press either the
or button to change the default value (HP)
to the new value (CO).
• Press the
button to send the configuration to the unit, which
will confirm with a “beep”.
• Press
button to save the new remote control configuration.
For other available configuration options, see table VIII.
Note:
When 30 seconds have elapsed and no buttons have been
pressed, the remote controller will automatically exit the
configuration menu and the procedure has to be restarted.