DIAGNOSIS AND SOLUTION (CONT)
Refrigerant Leakage Detection (EL0C)
Description: Define the compressor’s evaporator coil temperature (T2) starts running as Tcool.
In the initial 5 minutes after the compressor starts, if T2<Tcool-1.8
F (1C) is not maintained for 4 seconds and the compressor runs at a frequency is 
higher than 50Hz however it does not maintain for a minimum of three minutes and this issue occurs 3 times, the LED displays the failure code and the 
unit turns off.
Recommended parts to repair:
• T2 Sensor
• Indoor PCB
• Additional refrigerant
Troubleshooting
Power o the unit. Restart the unit 2 minutes later.
Are there 
any leaks?
Check the system for blocks and
clear any if present.
Does a problem remain?
Place your hands in front of the
indoor air outlet. 
YES
Is cool air 
blowing from the 
indoor air outlet?
Is it securely 
attached?
Replace the 
indoor PCB.
YES
Check the T2 sensor.
YES
Check the system for leaks.
NO
NO
Repair the leak and
recharge the refrigerant.
YES
NO